Fig.10:
Re lay Ad der M od ule
Fig.11:
HU DAC T-100 Dig ital C om m un icato r M od ule
6.6 RE LAY ADD ER M OD UL E (M od el HR M -1008 A)
P2
Data Cable to P5 of Main Fire
Alarm Module or to previous
Adder Module.
P1
Data Connector for next Adder
Module.
P4
Power Connector to P6 of Main
Fire Alarm Module or to previous
Adder Module.
P3
Power Connector for next Adder
Module.
JW1 Continuity Jumper
removed if
there are any more
Adder
Modules
installed.
Jumper
JW6
on the Main Fire Alarm
Module must be removed if there are
any
Adder Modules
installed.
The HRM-1008A requires 8
Display Points
.
6.7 HUDACT DIGITAL CO MM UNICATOR MO DULE (M odel HUDACT-100)
P1
Cable to P8 on the Main Fire
Alarm Board.
P2
RS-485 Connection for future
expansion.
P3
Not used.
P4
C o n n e c t o r f o r C F G - 1 00
Configuration Module.
I2
Status Indicator LED for Telco
Line #1; Red when the line is in
use, Amber when there is a line
fault.
I1
Status Indicator LED for Telco
Line #2; Red when the line is in
use, Amber when there is a line
fault.
Jumper
JW4
on the Main Fire Alarm
Module must be removed if a
HUDACT-100
is installed. Note that this
module cannot be installed if a
City Tie
Module
is used.
Please see HUDACT-100 Manual for more information.
6.8 POLARITY REVERS AL and CITY TIE M ODU LE (MO DEL: HPR-100)