Fig.23:
Co nfig ura tion Ind icato rs an d C on trols
10.0 SYSTEM CONFIGURATION
10.1 INTRODUCTION TO CONFIGURATION:
Configuration of the HCP Series 1000 Fire Alarm Control Panel is performed by a combination of
Co nfig ura tion DIP
Switch
settings and button presses. Circuit (Zone) related operations are correlated to their respective Disconnect
Switches.
The
Configuration DIP Switches
are accessible from the Main Display Module after removing a protective lexan
cover with two screws, and are labeled as
CONFIG. 1 to 8
. The C ircuit (Zone) Disconnect Switches are re-defined as
Circ uit (Zone) Select
during C onfigura tion. C aution sho uld be use d to reset the Z one Disc onn ect S witch es b ack to
the des ired s ettings befo re ex iting configu ration m ode . Normal sys tem operatio n is susp en de d w hile
Configuration
Mode
is active .
Configuration M ode
is entered whenever any of the Configuration DIP Switches are set as per
functions listed in the
Co nfig ura tion DIP Sw itch Fu nction Ta ble
and exited by turning them all OFF (put switches
in the bottom or OF F positions), then performing a
SYSTEM RESET
!
W
HILE IN
C
ONFIGURATION
M
ODE THE
F
IRE
A
LARM
C
ONTROL
P
ANEL IS NOT
O
PERATING
!!
Three buttons and LED indicators are re-defined in
Configuration Mode
...
Acknowledge (referred to as the
Yellow Button
):
T his becomes a
“
Select Setting
”
button and the LED
indicator may show current status of a function.
General Alarm (referred to as the
Red Button
):
T h i s b e c o m e s a
“
C o n f ir m a t i o n
”
b u t t o n f o r s o m e
functions, used together with the
Yellow Button
.
Buzzer Silence (Blu e Bu tton):
This button performs its normal function of silencing the
buzzer.
All other buttons are non-functional during Configuration Mode.
The figure to the right shows the positions of the
Configuration DIP Switch
and the
Yellow and
Red Buttons
. Each has a matching LED indicator
of the sam e color. N ote tha t the labels
“Acknowledge”
and
“General Alarm”
will only be
shown in an HCP 1000 co nfigured as a Two-
Stage System.
Configuration Functions
are selected by the
Configuration DIP Switches as follows in the
Configuration DIP Sw itch Fu nction Ta ble
. No te
that a Switch position of “0" is
“
OFF
”
(bottom
position) and
“1" is “ON” (top position).