9.1 COM MO N INDICATORS:
Buzzer:
The Buzzer is activated by any of the following ...
Fire Alarm
-
Steady
Supervisory Alarm
-
Steady
Trouble
-
Trouble Flash Rate
If the Buzzer is turned on in response to a Non-Latching Trouble or Supervisory, it will be turned off if the condition causing it goes away and
there is no other reason for it to be on.
AC On LED:
The AC On Indicator is activated steady green while the main AC power is within acceptable levels. It is turned off when the level falls below
the power-fail threshold and the panel is switched to standby (battery) power.
Common Alarm LED:
The Common Alarm Indicator turns on steady red whenever the Panel is in Alarm as a result of an alarm on any Initiating Circuit or activation
of the manual red General Alarm Button (if the Panel is set for Two Stage Operation). Since all Alarms are latched until the Panel is reset, the
Indicator will remain on until then.
Common Supervisory LED:
The Common Supervisory Indicator turns on steady amber when there is a Supervisory Alarm in the Panel, as the result of any Latching or
Non-Latching Supervisory Circuit. The Indicator is turned off if all Non-Latching Supervisory Circuits are restored and there are no Latching
Supervisory Circuits active. Latching Supervisory Alarms remain active until the Panel is reset.
Common Trouble LED:
The Common Trouble Indicator flashes amber at the Trouble Flash Rate when there is any Trouble condition being detected on the panel. It
is turned off when all Non-Latching Troubles are cleared.
Remote Failure LED:
The Remote Failure Indicator is flashed amber at the Trouble Flash Rate if there is trouble detected at a City Tie, HUDACT, or if there is
communication trouble detected with a Remote Annunciator or if a Remote Annunciator reports a local trouble. It is turned off if these conditions
go away.
Fire Drill LED:
The Fire Drill Indicator turns on steady amber while Fire Drill is active.
Acknowledge LED:
If the Panel is configured as Two Stage, the Acknowledge Indicator flashes amber at the Fast Flash Rate while the Auto General Alarm Timer
is timing out. It turns on steady amber when that Timer is cancelled by activating the Acknowledge or Signal Silence buttons. If the Auto General
Alarm Timer times-out and puts the Panel into General Alarm, the Indicator is turned off.
General Alarm LED:
In Two Stage Operation only, the General Alarm Indicator is activated steady red when General Alarm is activated due to the red General Alarm
button being pushed, a General Alarm Initiating Circuit being activated, or the Auto General Alarm Timer timing out. Once the General Alarm
Indicator has been turned on it will stay active until the Panel is reset.
Configuration / Test Mode LED:
The Configuration / Test Mode Indicator is turned on steady amber to indicate that the Panel is in either Walk-Test or Configuration Mode.
If the Panel is left in either Mode for over an hour with no operator activity, this Indicator will flash at the Trouble Rate.
Auxiliary Disconnect LED:
The Auxiliary Disconnect Indicator is flashed amber, at the Trouble Rate, when the Auxiliary Disconnect button is pressed. It is turned off when
the button is pressed a second time. When on, it indicates that Common Alarm and Common Supervisory Relays are not activated, and
Programmable Relays (if Disconnect is enabled) are not activated. The City Tie Module is also inactive if installed.
Signal Silence LED:
The Signal Silence indicator is flashed amber, at the trouble rate when Indication Circuits are Silenced either by the Signal Silence button, or
by the Auto Signal Silence Timer. It is turned off when the Signals are re-sounded by a subsequent Alarm.
Battery Trouble LED:
The Battery Trouble Indicator flashes amber at the Trouble Rate when the Battery is either low (below 20.4 VDC), or disconnected.
Ground Fault LED:
The Ground Fault Indicator flashes amber at the Trouble Rate when the Ground Fault Detector detects a Ground Fault on any field wiring. It
is turned off when the Ground Fault is cleared.