- 39 -
HRS Series Soft Starter( 400
KW~630KW
)
Model
Rated
power
(kw)
Rated
current
(A)
SCPD
specificati
on
Supporting circuit
breaker model(QF)
Supporting
bypass
contactor
model
(KM)
Specification
of primary
cable
Remark
HRS-400-B-G3
400
800
/
DZ20Y^1250/3300
1000A
CJ40-800
50 x 6mm
2
copper wire
For 400KW and above,
the cable is used to
lead the wiring, and the
method is six in and
three out. Rated power
rated current refers to
the max. value of the
soft starter.
HRS-450-B-G3
450
900
/
DZ20Y1250/3300
1000A
CJ40-1000
50 x 6mm
2
copper wire
HRS-500-B-G3
500
1000
/
DZ20Y1250/3300
1250A
CJ40-1000
60 x 8mm
2
copper wire
HRS-630-B-G3
630
1200
/
DZ20Y1250/3300
1250A
CJ40-1200
60 x 8mm
2
copper wire
Note: The specification parameter list of peripheral accessories is for reference