- 14 -
②
Structural dimension of product for HRS Series 75KW or more
Model
Rated
power (kw)
Rated
current
(A)
Outer dimension(mm) Installation dimension(mm)
Gross
weight(kg)
W1
H1
D
W2
H2
d
HRS-075-B-G3
75
150
260
435
200
225
360
M8
20
HRS-090-B-G3
90
180
260
435
200
225
360
M8
20
HRS-115-B-G3
115
230
260
435
200
225
360
M8
20
HRS-132-B-G3
132
260
260
435
200
225
360
M8
20
HRS-160-B-G3
160
320
260
435
200
225
360
M8
20
HRS-185-B-G3
185
370
260
435
200
225
360
M8
20
HRS-200-B-G3
200
400
260
435
200
225
360
M8
20
HRS-220-B-G3
220
440
260
435
200
225
360
M8
20
HRS-250-B-G3
250
500
290
460
200
255
390
M8
30
HRS-280-B-G3
280
560
290
460
200
255
390
M8
30
HRS-320-B-G3
320
640
290
460
200
255
390
M8
30
HRS-400-B-G3
400
800
330
485
200
295
405
M8
36
HRS-450-B-G3
450
900
330
485
200
295
405
M8
36
HRS-500-B-G3
500
1000
330
485
200
295
405
M8
36
HRS-630-B-G3
630
1200
410
550
230
375
470
M8
56
3.2 Requirements of installation
Direction of installation
①
The soft starter must be installed in the vertical direction, not upside down, it should be installed on a firm structure with
screws.
②
The soft starter must generate heat when it is running. To ensure the passage of flowing air, The design leaves a certain
amount of space. The generated heat is dissipated upwards, so do not install under heat-sensitive equipment.
③
The main circuit uses top in and bottom out, and the wire should ensure sufficient carrying capacity of current.