background image

 

30 

 

05.17 207646 Rev.103

 

 

EKWXA│EKWXBA

 

AIR-COOLED WATER CHILLERS 
AXIAL FANS 

APPENDIX: SAFETY DATA R410A  

 

Refrigerant Data

 

Safety Data: R410A

 

General Precautions 

Do not inhale concentrated vapours. Their concentration in the atmosphere should 
not  exceed  the  minimum  preset  values  and  should  be  maintained  below  the 
professional threshold. Being weightier than the air, the vapour concentrates on the 
bottom, in narrow areas. T here fore, the exhaust system must work at low level. 

Respiratory System Protection 

If you are in doubt about the concentration in the atmosphere, it is recommended to 
wear a respirator approved by an accident prevention Authority, of the independent 
or oxygen type. 

Storage 

Cylinders  must  be  stored  in  a  cool,  dry  and  properly  ventilated  storage  area  away 
from  heat,  flames,  corrosive  chemicals,  flumes,  explosives  and  be  otherwise 
protected from damage. Keep a temperature below 52°C. 

Protective Clothing 

Wear overalls, protective gloves and goggles or a mask. 

Accidental Release Measures 

IIt  is  important  to  wear  protective  clothing  and  a  respirator.  Stop  the  source  of  the 
leak, if you can do this without danger. Negligible leaks can be left evaporating under 
the sun, providing that the room is well ventilated. Considerable leaks: ventilate the 
room. Reduce the leak with sand, earth or other absorbing substances. Make sure 
that the liquid does is not channelled into gutters, sewers or pits where the vapours 
are likely to create a stuffy atmosphere. 

Disposal 

The best method is recovery and recycling. If this method is not practicable, dispose 
according  to  an  approved  procedure,  which  shall  ensure  the  absorption  and 
neutralization of acids and toxic agents. 

Fire Fighting Information 

R410A: Not flammable in the atmosphere. 

Cylinders 

The cylinders, if exposed to fire, shall be cooled by water jets; otherwise, if heated, 
they may explode. 

Protective Fire Fighting Equipment 

In case of fire, wear an independent respirator and protective clothing. 

 

 

Summary of Contents for EKWXA 7002.4

Page 1: ...enance Manual 05 17 207646 Rev 103 EKWXA EKWXBA AIR COOLED WATER CHILLERS AXIAL FANS Models 7002 4 8002 4 9002 4 Cooling Capacities from 178 3 kW to 213 6 kW Heating Capacities from 194 9 kW to 244 2...

Page 2: ...efficiency adaptability usability and practical solutions This has been the hallmark of our product catalogue The versatility of our factory allows us to contribute solutions almost tailored to each p...

Page 3: ...IBUTION 13 Model 7002 4 13 Models 8002 4 9002 4 13 INSTALLATION LOCATION 14 UNIT SETTLEMENT 14 WATER DRAIN 14 ELECTRICAL CONNECTIONS 14 SERVICE AREA 15 Model 7002 4 15 Models 8002 4 9002 4 15 OPERATIO...

Page 4: ...dels 8002 4 9002 4 21 System Parameters 22 Regulation Parameters 23 Compressors 23 Alarms 24 HYDRONIC KIT 26 TECHNICAL DATA 26 OPERATING LIMITS 27 MAINTENANCE 27 CONSERVATION AND CLEANING 27 LUBRICANT...

Page 5: ...built in a way that does not pose a risk to the health and safety of people Appropriate project solutions have been adopted to eliminate the possible causes of risk in the installation Packaging and...

Page 6: ...be dangerous because the system is under pressure because some of its elements have high temperatures and include electrical components Do not install the unit in explosive atmosphere ATTENTION Only...

Page 7: ...low driven by the fan itself Ready for outdoor installation totally closed with permanent lubrication It consists of aluminum blades designed to obtain a low sound level inserted into the outer rotor...

Page 8: ...23 5 2 x 24 COMPRESSOR Type SCROLL Number of compressors 4 Number of power stages 4 Maximum current for operating circuit A 71 80 89 Locked rotor current A 249 264 309 Oil type POE 160 SZ Oil volume L...

Page 9: ...62 1 416 3 SOUND LEVEL Sound power dB A 92 8 94 7 94 8 Sound pressure 5m 5 dB A 71 72 9 73 WEIGHT AND DIMENSIONS Large mm 3200 Width mm 2250 High mm 2150 Net weight of heat pump units EKWXBA kg 1720 1...

Page 10: ...nd stable bear in mind that the heaviest part is where the compressor is installed Always transport the unit in its original packaging to the place of installation Lifting through crane STORAGE If the...

Page 11: ...COOLED WATER CHILLERS AXIAL FANS INSTALLATION DIMENSIONS Model 7002 4 1 Water inler 3 2 Water outlet 3 3 Electrical panel 4 Main switch 5 Electrical connection input 6 Optional electrical connection...

Page 12: ...LED WATER CHILLERS AXIAL FANS INSTALLATION DIMENSIONS Models 8002 4 9002 4 1 Water inler 3 2 Water outlet 3 3 Electrical panel 4 Main switch 5 Electrical connection input 6 Optional electrical connect...

Page 13: ...ing pump 233 246 194 181 185 187 248 246 1720 Cooling only 234 247 181 173 176 184 244 247 1686 Models 8002 4 9002 4 WEIGHT DISTRIBUTION kg R1 R2 R3 R4 R5 R6 R7 R8 TOTAL 8002 4 Heating pump 229 241 20...

Page 14: ...r larger than unit drain connection depending on the line length and general building configuration The condensate line should be pitched a minimum 2 for proper water evacuation When drain line is exp...

Page 15: ...15 05 17 207646 Rev 103 EKWXA EKWXBA AIR COOLED WATER CHILLERS AXIAL FANS INSTALLATION SERVICE AREA Be sure to respect the measures for a proper operation of the unit Model 7002 4 Models 8002 4 9002 4...

Page 16: ...n 7002 4 5002 4 9002 4 Bomba de Calor 7002 4 5002 4 9002 4 EKWXA EKWXBA 60 25 30 35 40 45 50 55 15 10 5 0 5 10 15 LWT C Temperatura exterior Outdoor temperature T mperature x 7 10 5 0 5 10 15 20 25 2...

Page 17: ...ain Functions of the Control System Regulates water temperature Service hour counter for compressors and water pumps optional Intake and outlet water temperature reading displays as well as pressure r...

Page 18: ...t must be started up once again ESC Pressing this key leads to a shortcut to the ALARMS menu RETURN This key takes the user to the MAIN MENU screen if it is pressed in the START MENU screen It is also...

Page 19: ...meters or system setting options Level L0 User Access no password required Level L1 User Maintenance Access Level L2 Manufacturer authorized Access ONLY Inputs Outputs DISPLAY A DISPLAY B ALARMS WARNI...

Page 20: ...e circuit 1 only heat pump 4 Cond evap pressure Cool Heat circuit 1 Thermal outdoor fans circuit 1 Antifreeze resistance circuit 1 5 Evap cond pressure Cool Heat circuit 1 Safety high pressure switch...

Page 21: ...ays valve circuit 1 only heat pump 4 Evap cond pressure Cool Heat circuit 1 Thermal outdoor fans circuit 1 Antifreeze resistance circuit 1 5 Cond evap pressure Cool Heat circuit 2 Safety high pressure...

Page 22: ...s indicates the operational mode for restart System HEAT COOL Indicates current operating mode HEAT COOL and it also allows switching between modes If the unit is running it stops before switching ope...

Page 23: ...ling more By default this value is 6 0 C High Limit Set point Temperature This is used to set the highest limit of the Set point temperature in cooling more By default this value is 17 0 C Heating Set...

Page 24: ...ressor 2 exceeded Notification A63 Service Hours For Compressor 3 Exceeded Notification A64 Service Hours For Compressor 4 Exceeded Notification A7A Intake water probe Automatic OFF OFF OFF OFF A7B Ou...

Page 25: ...ater pump 1 Automatic OFF AP2 Thermal protection water pump 2 Automatic OFF AP9 Operation reserved pump Notification E10 EEV Connection Alarm Circuit 1 Manual OFF C1 E12 EEV Reheat Temperature Alarm C...

Page 26: ...Hz 400 3 50 Number of Heat Pump 2 Reserve Heat Pump Option SI Maximum weight Heat Pump H K full of water kg 2245 2278 2284 LOW PRESSURE PUMP Model CEA 370 2 Rated Power per unit kW 1 5 Maximum Curren...

Page 27: ...al circuit Make sure that all electrical connections wires contactors and terminals are properly tight Record the readings for volts and amperes of each compressor and fan motor Verify the starting cu...

Page 28: ...h higher available pressure With this accessory is included the control of condensation of the equipment SOFT STARTER Soft starter to minimize peak currents at the compressor start ELECTRONIC EXPANSIO...

Page 29: ...cur An individual exposed to high concentrations of R410A must be given medical attention immediately Adequate ventilation must be provided at all times Recommendations Semiotics or support therapy is...

Page 30: ...emperature below 52 C Protective Clothing Wear overalls protective gloves and goggles or a mask Accidental Release Measures IIt is important to wear protective clothing and a respirator Stop the sourc...

Page 31: ...31 05 17 207646 Rev 103 EKWXA EKWXBA AIR COOLED WATER CHILLERS AXIAL FANS We reserve the right to add modifications without prior notice...

Reviews: