9
05.17 207646 Rev.103
EKWXA│EKWXBA
AIR-COOLED WATER CHILLERS
AXIAL FANS
TECHNICAL DATA
EKWXA/EKWXBA
7002.4
8002.4
9002.4
OUTDOOR HEAT EXCHANGER
Type
Aluminum fin coil and copper tubing
Quantity
2
Front surface of the exchanger
m
2
5,18 + 5,18
INDOOR HEAT EXCHANGER
Type
PLATES (Water / Refrigerant)
Quantity
2
Evaporator water flow
m
3
/ h
33
35,5
37
Evaporator pressure drop
KPa
63
70,8
77,5
Water volume
L
8,4
8,4
8,4
Anti-ice resistance
W
100
WATER CONNECTIONS
Type
SLOTTED
– Victaulic type
External diameter
(‘’)
3 ''
3 ''
3 ''
ELECTRIC SPECIFICATIONS
Supply voltage
V / ~F / Hz
400V - 3+N 50Hz
Maximum intensity
A
156,2
178,2
196,6
Starting current (AC)
A
334,7
362,1
416,3
SOUND LEVEL
Sound power
dB(A)
92,8
94,7
94,8
Sound pressure (5m)
(5)
dB(A)
71
72,9
73
WEIGHT AND DIMENSIONS
Large
mm
3200
Width
mm
2250
High
mm
2150
Net weight of heat pump units - EKWXBA
kg
1720
1753
1759
Net weight of cooling only units - EKWXA
kg
1686
1719
1725
Note:
(1)
COOLING MODE: Outdoor temperatura 35ºC, Water inlet temperature 12ºC, Water outlet temperature 7ºC.
(2)
HEATING MODE: Outdoor temperature 7ºC D.B. / 6ºC W.B., Inlet temperature 40ºC, Water outlet temperature 45ºC.
(3)
TOTAL ABSORBED CAPACITY: Absorbed power by the equipment in Cold or Heat conditions indicated above according to UNE-EN-14511-2: 2013.
(4)
GWP: Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO
2
, calculated in terms of 100-year warming potential.
(5)
Measurement conditions on the free field, directivity 2 and 1,5 meters above the floor.