26
05.17 207646 Rev.103
EKWXA│EKWXBA
AIR-COOLED WATER CHILLERS
AXIAL FANS
HYDRONIC KIT
TECHNICAL DATA
KRONO 2
series
7002.4
8002.4
9002.4
HYDRONIC KIT
Expansion Vessel Volume
l
50
Deposit Inertia Volume
l
300
Available Pressure M H.K. Without Tank
kPa
104,2
118,4
129,2
Available Pressure M H.K. With Tank
kPa
114
129,8
141,6
Water Flow
m
3
/h
33
35,5
37
Connection Type
Slotted - Victaulic
Connection Diameter
(“)
3
HEAT PUMP OPTION
Power Supply
V/~/Hz
400/3/50
Number of Heat Pump
2
Reserve Heat Pump Option
SI
Maximum weight: Heat Pump + H.K. (full of water)
kg
2245
2278
2284
LOW PRESSURE PUMP
Model
CEA 370/2
Rated Power (per unit)
kW
1,5
Maximum Current (One Pump Operation)
A
3,4
Locked Rotor Current (One Pump)
A
28
Available Pressure M H.K. Without Tank
kPa
66
46,4
32,2
Available Pressure M H.K. With Tank
kPa
56,2
35,1
19,9
HIGH PRESSURE PUMP
Model
CEA 370/5
Rated Power (per unit)
kW
3
Maximum Current (One Pump Operation)
A
5,9
Locked Rotor Current (One Pump)
A
51,2
Available Pressure M H.K. Without Tank
kPa
157,9
139,2
125,5
Available Pressure M H.K. With Tank
kPa
148,1
127,8
113,2