10
CCHBA-CCHA
HORIZONTAL CONDENSER UNITS
WITH COMPRESSOR AND CENTRIFUGAL FAN
IOM_CCHBA- CCHA_201a1201_208029_200201_EN
TRANSPORT & RECEPTION
INSPECTION AT RECEPTION
It is advisable to examine the equipment carefully upon reception.
Check that the equipment has not been damaged during transport and that it is complete with all the parts
specified in the order and/or the options stated in the order. If this is not the case please contact the
transport company immediately (within 48h).
Verify the correct voltage of the nameplate and make sure it is in accordance with local power supply.
In case of any flaw or anomaly detected, please contact HITECSA.
RIGGING
Before moving the unit, make sure that all panels are fixed properly.
Raise and put the equipment down carefully.
Do not tilt the unit more than 15 degrees during transportation.
Always transport the unit in its original packaging to the place of installation.
All units come with a particular rigging diagram of that model similar to the one shown below. Be sure to
hoist the machine through the points indicated in the diagram.
Make sure that the unit is balanced, stable and without any deformations during the lifting operations.
STORAGE
If the equipment is going to be stored before the installation, please follow the following instructions in order to avoid
damages, corrosion or deterioration:
Move the equipment carefully.
Do not place the unit in places exposed to ambient temperatures above 50ºC and preferably keep the unit away
from direct sunlight.
Avoid placing the unit with plastic wrapping protection under the sun as the pressure of the circuits could reach
values that could lead to the activation of the safety valves.
Moreover, with decreasing temperatures water condensation may occur inside the machine and the plastic
wrap.
Avoid placing other objects on top of the unit (unless this is done within the limits of the overlap planes indicated
on the packaging, etc. Follow these indications).
Avoid prolonged storage before installation, water penetration, dust and objects in general due to invasion or
biological, meteorological and/or human impacts.
Minimum storage temperature: -10ºC
Maximum relative humidity: 90%.