Hitecsa CCHBA/CCHA 1001 Installation, Operation & Maintenance Manual Download Page 38

 

38 
 

IOM_CCHBA- CCHA_201a1201_208029_200201_EN

 

CCHBA-CCHA

 

HORIZONTAL CONDENSER UNITS 
WITH COMPRESSOR AND CENTRIFUGAL FAN

 

 

MAINTENANCE 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

It is advisable to schedule maintenance visits every 1,000 operating hours, as well as at the end of summer. Please keep 
an updated record of all maintenance operations and readings (maintenance sheet).

 

Repairing operations must be carried out by trained specialists only.  

 

Wear safety shoes and gloves adapted to each operation. 

 

Please observe the safety regulations and the worker’s protection rules for any maintenance and service operation (EN 
50 110, IEC 364). 

 

No maintenance work with running fans! Warning because fans can rotate without having power supply, e.g. pushed by 
air currents.

 

Make use of fire protections in brazing operations.

 

In case of leakage, any manipulation and/or recovery of refrigerant shall be completed by qualified and authorized 
personnel in accordance with the valid regulation. Add the quantity of oil that has been lost. 

 

 

CONSERVATION AND CLEANING 

 

Precaution! 

 

Do not use aggressive cleaning products nor varnish solvents.  

 

Avoid  water  penetration inside  the  motor  or  to  the  electronic  components  (e.g.  through  the  direct  contact  with  joints or 
holes of the motor), observe the protection class (IP).

 

 
Electrical circuit

: Make sure that all electrical connections 

–wires, contactors and terminals- are properly tight. Register the 

readings  of  kW  and  amperes  at  each  compressor  and  fan  motor  phase.  Verify  the  starting  current.  Check  the  start  current. 
Check that all mechanical components, pressure switches and so on are working properly.  

Refrigeration  circuit

:  Check if  there is  any  refrigerant  leak,  noises  or  vibration.  Proceed  to  measuring  temperatures  and/or 

pressures  of  components  of  the  most  important  components  of  the  system  and  register  them  on  the  maintenance  sheet 
(compressor discharge and aspiration, expansion valve, exchangers’ inlet and outlet, etc…). 

Compressor: 

Check regularly the lubricant level, the presence of vibrations or noise and the motor insulation. 

Coils

: At least once a year clean the condenser coils with water and detergent, then dry with air at low pressure. Never clean 

with a wire brush, water and/or air at high pressure (max. 6 bar). 
 

Fans: 

Check the direction of rotation of the fans, verify their carriers. Check the transmission elements and the operating status. 

Before working on the fan make sure that it is disconnected from the main power supply even though it is already stopped and 
control that nobody may start it during the intervention.  
A regular inspection of the unit is required to avoid dirt accumulation in propellers, turbines, motors and grids that could  entail 
risks and significantly shorten their life. The frequency will depend on the working conditions. 
Keep the airways of the fan free 

– danger of expulsion of objects! 

Check the free flow of the condensation water through the evacuation openings is necessary (if there are any).  
During cleaning operations be very careful not to unbalance the propeller or the turbine. 
In case of incorrect cleaning operations no guarantee is assumed regarding corrosion formation / paint adhesion for unpainted 
/ painted fans.  
To avoid humidity accumulation in the motor the fan must be operated during at least 1 hour at 80 to 100% of its maximum 
speed before cleaning!  

 

 

 

Before completing any service or maintenance operation, turn the main power switch off to avoid 

any personal injuries. Lock it so that nobody else than a qualified technician can switch it on. 

 

Before opening the electrical panel and having access to the inside of the machine it is MANDATORY 
to  disconnect  the  power  supply  hose  of  the  machine  which  MUST  BE  FREE  OF  VOLTAGE  for  this 
operation.

 

 

Summary of Contents for CCHBA/CCHA 1001

Page 1: ...1a1201_208029_200201_EN CCHBA CCHA HORIZONTAL CONDENSER UNITS WITH COMPRESSOR AND CENTRIFUGAL FAN Models 201 251 351 371 401 501 701 721 751 801 1001 1201 Cooling Capacities from 5 6 kW to 33 5 kW Hea...

Page 2: ...oning and cooling installations for over 35 years Our approach is based on efficiency flexibility and on practical solutions This has been the hallmark of our product catalogue The versatility of our...

Page 3: ...del 12 CCHBA CCHA 251 model 12 CCHBA CCHA 351 model 13 CCHBA CCHA 371 401 501 models 13 CCHBA CCHA 701 721 751 801 models 14 CCHBA CCHA 1001 model 14 CCHBA CCHA 1201 model 15 WEIGHT DISTRIBUTION KG 16...

Page 4: ...of the Th Tune internal temperature probe 27 Operation modes 27 Indoor Fan 28 Alarms 29 TH TUNE CONTROL 30 ALARMS DIAGNOSIS 30 TH TUNE Description of the alarm codes 30 PGD1 OR MINI PGD THERMOSTAT 31...

Page 5: ...ating the Data The continuous improvement in design and performance to which we are committed to gives us the right to modify the specifications of our products without prior notice Electrical Supply...

Page 6: ...orized manipulation reparation or modification of the unit will automatically invalidate the warranty Packaging and Replacement of Equipment The material of the package plastic bags insulating materia...

Page 7: ...ill carry out basic tasks only such as cleaning and replacement of filters or filter cleaning excluding the refrigerant filters etc Prevent access to children to avoid that they play with the equipmen...

Page 8: ...0 400 Fin Spacing mm 1 8 Tube Diameter mm 3 8 FAN Type Centrifugal double suction Model 9 9 DD 10 10 DD 10 10 DD 12 9 DD 12 9 DD 12 9 DD Motor Power kW 0 37 0 37 0 44 0 55 0 55 1 10 Voltage V 230 1 23...

Page 9: ...0 605 0 900 1 190 Fin Spacing mm 1 8 Tube Diameter mm 3 8 FAN Type Centrifugal of Double Suction Model 12 12 DD 12 12 DD 12 12 SS 12 12 SS 12 12 SS 12 12 SS Motor Power kW 1 1 1 1 1 5 1 5 2 2 4 0 Vol...

Page 10: ...the one shown below Be sure to hoist the machine through the points indicated in the diagram Make sure that the unit is balanced stable and without any deformations during the lifting operations STORA...

Page 11: ...the transmission of noise and vibration Check that the direction of the sound level will not disturb anybody The standard version of this equipment has been designed for installation inside a building...

Page 12: ...l LEGEND 1 Motor 2 Fab 3 Indoor drainage 3 4 4 Heat exchanger 5 Compressor 6 Electrical Panel 7 Refrigerant connections 8 External Pressure Tap for Monitoring 9 Power supply LEGEND 1 Motor 2 Fan 3 Ind...

Page 13: ...ptional Legend 1 Motor 2 Fan 3 Drainage 3 4 4 Heat Exchanger 5 Compressor 6 Electrical Panel 7 Refrigerant Connections 8 External Pressure Tap for Monitoring 9 Main Switch 10 Power Supply Standard Opt...

Page 14: ...Heat Exchanger 3 Turbine 4 Turbine Motor 5 Electrical Panel 6 Drainage 3 4 7 Main Switch 8 Electrical Connections 9 External Pressure Tap for Monitoring 10 Refrigerant Connections Standard Optional L...

Page 15: ...1201_208029_200201_EN INSTALLATION DIMENSIONS CCHBA CCHA 1201 model Standard Optional Legend 1 Compressor 2 External Heat Exchanger 3 External Pressure Tap for Monitoring 4 Electrical Panel 5 Turbine...

Page 16: ...es below 0 degrees thermal insulation or electrical heating wires shall be used to prevent the water from freezing and avoid the possible following tube damages Install a siphon with the appropriate d...

Page 17: ...e line pressure drop The refrigerant circulation speed The refrigerant mass in the system The length of the interconnection pipes please contact Hitecsa for lines longer than 50 meters Discharge lines...

Page 18: ...The indoor unit is installed at the same level as the outdoor unit raise the suction line to a higher level than the indoor heat exchanger in order to avoid refrigerant return into the compressor dur...

Page 19: ...17 2 647 22 9 808 28 6 1 3 8 24 853 120 4 3 241 8 5 481 17 1 722 25 6 963 34 1 1204 42 6 1 5 8 34 1219 172 6 1 344 12 2 688 24 4 1033 36 6 1377 48 8 1721 60 9 2 1 8 61 2149 303 10 7 607 21 5 1213 43...

Page 20: ...could leave particles inside the pipe Reduce the number of brazing and remember that it should always be of the strong type In compliance with local laws the welder must be an authorized person A bad...

Page 21: ...devices must be installed by the installer according to the current local laws The interconnecting wires shall be protected by a tube or an electrical cable conduit cable tray etc ELECTRICAL DATA CCHB...

Page 22: ...power supply 2 single phase wires 230V 1 N 4 three phase wires 400V 3 N 1 Ground 2 Ground wire can go by main power supply 3 Curve D thermal circuit breaker differential 4 Main switch 5 Available powe...

Page 23: ...RIFUGAL FAN IOM_CCHBA CCHA_201a1201_208029_200201_EN INSTALLATION ELECTRICAL CONNECTION DIAGRAM pGD1 control or Mini pGD options Connection to pGD1 with 6 wire telephone cable for lines longer than 50...

Page 24: ...will not covered by Hitecsa s warranty The unit must not be supplied with any other voltage than that indicated on the serial plate The power supply to the unit must be within 10 of the voltage indica...

Page 25: ...ours of operation Observe at least 3 cooling cycle operations Due to the unit has frequency converters it is essential that the protection be at least 300mA to prevent power cuts caused by the activat...

Page 26: ...se the set screws of the motor pulley and turn the movable flange Open or close depending on the needs Open speed decreases 3 Tighten set screws 4 Place the belt in the pulley channel The closure or o...

Page 27: ...ive or negative that shall be added to the value of the probe A value equal to zero will not change the value of the probe Press keys FAN ON OFF and keep them pressed until a password is required Ente...

Page 28: ...ral button to select the desired schedule type Select if you want a different schedule day by day the same schedule for all week displays all days or one from Monday to Friday and other from Saturday...

Page 29: ...cheaper Setpoint value 8 30 t3 Start up or return to the normal setpoing 13 15 t4 Stop due to absence or setting down to a cheaper Setpoint value 15 30 t5 Start up or return to the main Setpoint valu...

Page 30: ...essure switch alarm circuit 1 Air air ALF7 Thermal alarm of the indoor fan Air air ALF6 Thermal alarm of the external fan compressor Air air ALPM Minimum pressure switch alarm Air air ALRF Lack of ref...

Page 31: ...n retrocedes un nivel en la pantalla principal muestra la ayuda FLECHA ARRIBA Movimiento en los men s o modificaci n de valores de los par metros de regulaci n TECLA ENTER Confirmaci n de los valores...

Page 32: ...y Day Time schedule pGD1 models as standard HIT005 You will have 4 types of start in time schedule and when the time schedule is ON the screen will display the word PHASE A Manual type by selecting th...

Page 33: ...tpoint that it is inside the section and the external out from the section Example From Monday to Thursday the program num 1 is activated internal Setpoint from 6 30 to 11 00 etc D ON OFF schedule typ...

Page 34: ...r set back one hour form 03 00 to 02 00 Example DST of 60 min Enabled from the first Monday of February at 10 00 goes off at 11 00 until the last Sunday of October at 3 00 goes back at 2 00 Time sched...

Page 35: ...he three keys until the screen of the next image right is displayed change the value Display address setting from 32 to 00 3 Remove the voltage of the board 4 Press the two keys alarm UP and give volt...

Page 36: ...cription pGD1 Optional HITSAA01 ALARM MESSAGES pGD1 Optional HITSAA01 Displayed message Type Alarms Clock card error or not connected Warning Alarms Probe B01 broken or disconnected Warning Alarms ThT...

Page 37: ...Alarm General Alarm of the Burner Alarm Severe Damaged Memory indication Warning Missing Clock or not working Alarm Maintenance of the unit Only indication Warning Alarms Severe Return Temperature Pr...

Page 38: ...important components of the system and register them on the maintenance sheet compressor discharge and aspiration expansion valve exchangers inlet and outlet etc Compressor Check regularly the lubric...

Page 39: ...st once a year Take into account the meteorological conditions e g in areas where falling leaves or the flight of seeds may obstruct the drain trap it will also be necessary to clean them at mid and l...

Page 40: ...cuum pump If leakage symptoms appear during operation proceed to a leak test A HCF detector is necessary in case of small leaks If a gas leak is detected proceed to removing and recuperating the entir...

Page 41: ...edly lethal There is risk of suffocation at higher concentrations due to the oxygen content reduction at the atmosphere Remove victim to fresh air keep it warm and at rest Supplemental oxygen if it is...

Page 42: ...mage Keep a temperature below 50 C Protective Clothing Wear overalls protective waterproof gloves and protective goggles or a mask Accidental Release Measures It is important to wear protective clothi...

Page 43: ...43 IOM_CCHBA CCHA_201a1201_208029_200201_EN CCHBA CCHA HORIZONTAL CONDENSER UNITS WITH COMPRESSOR AND CENTRIFUGAL FAN We reserve the right to add modifications without prior notice...

Reviews: