![Hitecsa CCHBA/CCHA 1001 Installation, Operation & Maintenance Manual Download Page 9](http://html1.mh-extra.com/html/hitecsa/cchba-ccha-1001/cchba-ccha-1001_installation-operation-and-maintenance-manual_2140035009.webp)
9
CCHBA-CCHA
HORIZONTAL CONDENSER UNITS
WITH COMPRESSOR AND CENTRIFUGAL FAN
IOM_CCHBA- CCHA_201a1201_208029_200201_EN
TECHNICAL SPECIFICATIONS
CCHBA- CCHA
701
721
751
801
1001
1201
CAPACITIES
Cooling Capacity (1)
kW
17.2
18.5
20.8
21.9
28.4
33.5
Heat Capacity (2)
kW
18.9
20.4
21.9
24.6
29.8
37.2
COMPRESSOR
Type
Scroll
Voltage
V/~/Hz
400 / 3+N / 50
REFRIGERANT
Type
R-410A
GWP (3)
2088
Load (4)
kg
5.7
5.7
5.9
6.7
9.0
9.5
HEAT EXCHANGER
Type
Aluminum fin coil and copper pipes
Frontal Area
m
2
0.605
0.605
0.605
0.605
0.900
1.190
Fin Spacing
mm
1.8
Tube Diameter
mm
3/8
FAN
Type
Centrifugal of Double Suction
Model
12/12 DD
12/12 DD
12/12 SS
12/12 SS
12/12 SS
12/12 SS
Motor Power
kW
1.1
1.1
1.5
1.5
2.2
4.0
Voltage
V
400 / 3+N
Nominal current input
A
3.5
3.5
3.4
3.6
4.7
9.2
1. Nominal cooling: Outdoor air temperature: 35 ºC. Condensation temperature: 40 ºC.
2. Nominal pump: Outdoor wet air temperature: 7ºC B.S. / 6ºC B.H. Evaporation temperature: 5ºC.
2. GWP: Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO
2
, calculated in terms of 100-year warming potential.
3.
Only units with “FLARE” valve as standard (not optional) are loaded with refrigerant, the rest of them are loaded with dry nytrogen.