Appendix
H:
Third-party racks
All VSP G series storage systems can be installed into third-party racks.
The following describes the requirements and guidelines for installing the storage
system into a third-party rack.
Third-party rack support
The storage system supports third-party racks that meet Hitachi Vantara specifications.
Observe the following mounting guidelines for third-party racks:
■
The VSP Gx00 models support any 4-post, EIA-310-D compliant rack that has
adequate airflow and weight capacity.
■
PDUs must be mounted properly, with no serviceability issues. The PDU receptacles
must face toward the back (not toward each other). The area behind the storage
system and between the vertical 19-inch mounting posts must be free of PDUs and
cable loops.
Hitachi Universal V2 Rack rail kits
Use rail kits to mount the Hitachi Virtual Storage Platform family storage system in a
Hitachi Universal V2 Rack.
The following tables list the rail kit information for the specified storage systems.
Table 6 Rail kits for VSP Gx00 models
Rail kit
Hitachi Universal V2 Rack
Third-party rack
Controller
UNI
1
UNI
1
DBS, DBL, and DBF drive
trays
CGR
2
UNI
1
DB60 dense intermix drive
tray
Use the rail kit supplied with the DB60 dense intermix
drive tray.
SVP server
Use the rail kit supplied with the SVP server.
Notes:
1. UNI: Universal rail kit A34V-600-850-UNI.
Appendix H: Third-party racks
Hitachi Virtual Storage Platform G200 Hardware Reference Guide
126