2–38
Installation Requirements
Hitachi Universal Storage Platform VM Installation Planning Guide
Heat Output, Power Consumption, and Air Flow
lists the power consumption, heat output, and air flow
requirements for the USP VM. These data apply to both 60Hz and 50Hz
storage systems. Fans are not required for customer-supplied racks. Airflow
is from front to back.
•
Table 2-10: Heat Output, Power, and Air Flow Specifications
Model Number
Heat Output (kW)
Power consumption (kVA) Air Flow (m
3
/min)
DKC615I-5
0.0291
0.30
4.3
DKC-F615I-B2
0.233
0.24
5.0
DKC-F615I-SBX
0.012
0.013
1.3
DKC-F615I-LGAB
–
0.015
–
DKC-F615I-PLUC
–
–
–
DKC-F615I-PHUC
–
–
–
DKC-F615I-PLEC
–
–
–
DKC-F615I-PHEC
–
–
–
DKC-F615I-UC0
–
–
–
DKC-F615I-UC1
–
–
–
DKC-F615I-EXC0
–
–
–
DKC-F615I-SX
0.005
0.005
–
DKC-F615I-S4GQ
0.013
0.013
–
DKC-F615I-DKA
0.097
0.100
–
DKC-F615I-EDKA
0.099
0.102
–
DKC-F615I-CX
0.005
0.005
–
DKC-F615I-C4G
0.015
0.015
–
DKC-F615I-C8G
0.019
0.020
–
DKC-F615I-C16G
0.019
0.020
–
DKC-F615I-8S
0.146
0.150
–
DKC-F615I-8MFS
0.146
0.150
–
DKC-F615I-8MFL
0.146
0.150
–
DKC-F615I-8FS
0.130
0.135
–
DKC-F615I-16FS
0.146
0.150
–
DKC-F615I-1FL
–
–
–
DKC-F615I-1FS
–
–
–
DKC-F615I-SVP
0.073
0.075
–
DKC-F615I-SVPV
0.073
0.075
–
DKC-F615I-MDM
0.006
0.006
–
DKC-F615I-72KS
0.020
0.021
–
DKC-F615I-146KS
0.020
0.021
–
DKC-F615I-300KS
0.020
0.021
–
DKC-F615I-0R7HS
0.018
0.019
–