Installation Requirements
2–9
Hitachi Universal Storage Platform VM Installation Planning Guide
Service Clearance, Floor Cutout, and Floor Load Rating
This section describes the service clearance requirements (a + b) for the
Universal Storage Platform VM storage system in the HDS-supplied rack,
based on the floor load rating and the clearance (c) and required floor
cutouts for cabling.
•
Single rack:
shows the service clearance and floor cutout
requirements for the single rack configuration.
shows the floor load rating and clearance requirements for this
configuration.
•
Two racks:
shows the service clearance and
floor cutout requirements for the twin rack configuration.
shows the floor load rating and clearance requirements for
this configuration.
•
Figure 2-4: Service Clearance and Floor Cutouts: Single Rack
DKC-F605I-200S1
0.5
—
—
—
Table 2-2: Component Specifications: Weight and Dimension
Model Number
Weight (kg)
Dimension (mm)
Width
Depth
Height
(Unit : mm)
Floor cutout area for cables
Caster
Screw jack
Service clearance
G
Grid panel (over 450mm x 450mm)
601
Front
G
DKC615
a
B
195
65 125
65
835
63 90
74
61.5
457
482
601
c *1
3250
1050
1100
Front
1050.00
575
601
Rear
DKC615
125
200 or more
355
482
215
62
125
1100
565
*1: The proper side clearance dimensions should be secured
corresponding to the 19-inch rack specifications.
*1 *1