6-7. Outdoor DC Fan Motor control circuit
This model uses DC Fan Motor which has a controller circuit built in the Motor.
This DC Fan Motor will rotate by control voltage apply to Vsp input. (V
(Voltage range: 1.7 to 7V DC)
Motor will output FG pulse by following this motor revolution.
indoor microcomputer.
This PWM control signal will convert to Vsp voltage by smoothing circuit. (R242 & C209)
rotation speed.
DC Fan Motor circuit has to match the Fan Motor revolution with instructed revolution. Such as...
FG feedback: Faster Instruction: Slower ... Decrease pulse width
FG feedback: Slower Instruction: Faster ... Increase pulse width
FG pulse is also used for Fan Motor failure detection.
Microcomputer will monitor FG pulse 30 seconds after start the fan motor. If there is no signal detected,
it will consider that the Fan Motor was malfunction and stop the operation. In this case, LD302 on main
R107 and IC4 are used for Fan Motor over current.
Vsp high : Faster ;
Vsp low : slower ;
Vsp lower than 1.7V
V
: stop
P.W.B. will blink 12 times. (Fan Motor lock detected)
FG pulse will feed back to Outdoor microcomputer 53 .
Outdoor microcomputer will output PWM control signal from 24 by following the instruction from
Fan motor will start to rotate when Vsp was proceeding over than 1.7V, and generate FG pulse by
1
24
53
46
45
44
HIC
Summary of Contents for Summit RAC-18YH6
Page 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS 18FH6 RAS 25FH6 INDOOR UNIT ...
Page 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC 18YH6 RAC 25YH6 OUTDOOR UNIT ...
Page 22: ... 20 CIRCUIT DIAGRAM MODEL RAS 18FH6 RAS 25FH6 RAS_AW_020 021_A2 2008 02 18 10 17 20 ...
Page 23: ... 21 RAC 18YH6 RAC 25YH6 MODEL RAS_AW_020 021_A2 11 17 06 11 18 AM 21 ...
Page 24: ... 22 RAS_AW_022_A3e 2008 02 19 16 33 22 ...
Page 25: ... 23 Silent RAS_AW_023_A3e 2008 03 06 20 58 23 ...
Page 27: ... 25 ...
Page 28: ... 26 ...
Page 30: ... 28 ...
Page 31: ... 29 ...
Page 47: ... 45 ...
Page 48: ... 46 ...
Page 50: ... 48 ...
Page 51: ... 49 ...
Page 52: ... 50 ...
Page 54: ... 52 ...
Page 77: ... 75 ...
Page 81: ... 79 ...
Page 82: ... 80 ...
Page 83: ... 81 ...
Page 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS 18FH6 RAS 25FH6 ...
Page 96: ...HITACHI AW NO 0024E RAS 18FH6 RAC 18YH6 RAS 25FH6 RAC 25YH6 ...