– 55 –
Outdoor temperature
(
)
1.19
0
1.69
10
10
2.23
20
2.75
30
3.22
40
3.62
R303 Voltage
(V
O
C
)
Table 6-2
-
Main P.W.B.
HIC
O.H. thermistor
DEF. thermistor
Outdoor temperature
thermistor
Microcomputer
AX-8V11
OH
DEF
Outdoor
temperature
59
63
64
0V
0V
0V
C302
0V
R303
R306
0V
R302
R305
C303
C304
R304
R301
0V
CN8
CN9
+5V
+5V
+5V
CN10
1
2
1
2
1
2
20
21
22
Fig. 6-12
6-4. Temperature Detection Circuit
The Over heat thermistor circuit detects the temperature at the surface of the compressor head, the Defrost.
thermistor circuit detects the defrosting operation temperature.
A thermistor is a negative resistor element which has the characteristics that the higher (lower) the temperature,
the lower (higher) the resistance.
When the compressor is heated, the resistance of the Over heat thermistor becomes low and voltage to a
pin
s
of microcomputer is increased.
Microcomputer compares the voltage at pin
s
with the internal set value, if it is exceeded the set value
microcomputer judges that the compressor is overheated and stops operation.
When frost forms on the outdoor heat exchanger, the temperature at the exchanger drops abruptly. Therefore
the resistance of the Defrost. thermistor becomes high and the voltage at pin
w
of microcomputer drops.
If this voltage becomes lower than the set value stored inside, the microcomputer starts defrosting control.
During defrosting operation the microcomputer transfers the defrosting condition command to the indoor
microcomputer via the circuit interface.
The microcomputer always reads the outdoor temperature via a thermistor (microcomputer pin
x
), an
transfers it to the indoor unit, thus controlling the compressor rotation speed according to the value set at the
EEPROM in the indoor unit, and switching the operation status (outdoor fan on/off, etc.) in the dehumidifying
mode.
The following shows the typical values of outdoor temperature in relation to the voltage:
<Reference>
When the thermistor is open, in open status, or is disconnected, microcomputer pins
s
,
w
,
x
are approx.
0V; when the thermistor is shorted, they are approx. 5 V, and LD301 blinks seven times.
However, an error is detected only when the OH thermistor is shorted; in such a case, the blinking mode
is entered 12 minutes after the compressor starts operation.
Summary of Contents for Summit RAC-18YH6
Page 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS 18FH6 RAS 25FH6 INDOOR UNIT ...
Page 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC 18YH6 RAC 25YH6 OUTDOOR UNIT ...
Page 22: ... 20 CIRCUIT DIAGRAM MODEL RAS 18FH6 RAS 25FH6 RAS_AW_020 021_A2 2008 02 18 10 17 20 ...
Page 23: ... 21 RAC 18YH6 RAC 25YH6 MODEL RAS_AW_020 021_A2 11 17 06 11 18 AM 21 ...
Page 24: ... 22 RAS_AW_022_A3e 2008 02 19 16 33 22 ...
Page 25: ... 23 Silent RAS_AW_023_A3e 2008 03 06 20 58 23 ...
Page 27: ... 25 ...
Page 28: ... 26 ...
Page 30: ... 28 ...
Page 31: ... 29 ...
Page 47: ... 45 ...
Page 48: ... 46 ...
Page 50: ... 48 ...
Page 51: ... 49 ...
Page 52: ... 50 ...
Page 54: ... 52 ...
Page 77: ... 75 ...
Page 81: ... 79 ...
Page 82: ... 80 ...
Page 83: ... 81 ...
Page 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS 18FH6 RAS 25FH6 ...
Page 96: ...HITACHI AW NO 0024E RAS 18FH6 RAC 18YH6 RAS 25FH6 RAC 25YH6 ...