Chapter 10 LCD display and operating for SJ300/L300P series
24 Multi-speed
4
>A024 SPEED
04S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
(NOTE 1) SJ300 series only .
(2/15)
No.
Function name
Display
Data range
25 Multi-speed
5
>A025 SPEED
05S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
26 Multi-speed
6
>A026 SPEED
06S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
27 Multi-speed
7
>A027 SPEED
07S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
28 Multi-speed
8
>A028 SPEED
08S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
29 Multi-speed
9
>A029 SPEED
09S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
30 Multi-speed
10
>A030 SPEED
10S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
31 Multi-speed
11
>A031 SPEED
11S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
32 Multi-speed
12
>A032 SPEED
12S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
33 Multi-speed
13
>A033 SPEED
13S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
34 Multi-speed
14
>A034 SPEED
14S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
35 Multi-speed
15
>A035 SPEED
15S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
36 Jogging
frequency
>A038 Jogging
F 01.00Hz
0.00
,
Starting frequency-9.99(Hz)
37 Jogging
selection
>A039 Jogging
Mode FRS
FRS(free-run on JG stop / invalid on running)/
DEC(stop decelerating on JG stop / invalid on
running)/
DB(DC braking on JG stop / invalid on
running)/
R-FRS(free-run on JG stop / valid on running
[JG after stop decelerating])/
R-DEC(stop decelerating on JG stop / valid on
running[JG after stop decelerating])/
R-DB(DC braking on JG stop / valid on
running [JG after stop decelerating])
38
Torque boost
Selection
>A041 V-Boost
Mode MANUAL
MANUAL (manual torque boost)/
AUTO(automatic torque boost)
39
Torque boost
selection, 2
nd
motor
>A241 2V-Boost
Mode MANUAL
MANUAL(manual torque boost)/
AUTO(automatic torque boost)
40
Manual Torque
boost
>A042 V-Boost
Code 01.0%
0.0 - 20.0
%
41
Manual Torque
boost
2
nd
motor
>A242 2V-Boost
Code 01.0%
0.0 - 20.0
%