Chapter 10 LCD display and operating for SJ300/L300P series
42
Manual Torque
boost
3
rd
motor
>A342 3V-Boost
Code 01.0%
0.0 - 20.0
%
(NOTE 1 )
43
Manual Torque
boost
point
>A043 V-Boost
F 05.0%
0.0 - 50.0
%
44
Manual Torque
boost
point, 2
nd
motor
>A243 2V-Boost
F 05.0%
0.0 - 50.0
%
45
Manual Torque
boost
point, 3
rd
motor
>A343 3V-Boost
F 05.0%
0.0 - 50.0
%
(NOTE 1 )
(NOTE 1) SJ300 series only .
(3/15)
No.
Function name
Display
Data range
46 1
st
control
>A044 Control
1st VC
VC / VP / FREE-V/F / SLV / 0SLV / V2
(NOTE 1)
47 2
nd
control
>A244 2Control
2nd VC
VC / VP / FREE-V/F / SLV / 0SLV
(NOTE 1)
48 3
rd
control
>A344 3Control
3rd VC
VC / VP
(NOTE 2 )
49
Output voltage
again
>A045 V-Gain
Gain 100%
20 - 100
%
50
DC braking
selection
>A051 DCB
Mode OFF
OFF(invalid) / ON(valid)
51
DC braking
frequency
>A052 DCB
F 0.50Hz
0.00 - 60.00 Hz
52
DC braking wait
time
>A053 DCB
WAIT 0.0s
0.0 - 5.0 s
53 DC
braking
power
>A054 DCB
STP-V 000%
0 - 100
%
(NOTE 3)
54 DC
braking
time
>A055 DCB
STP-T 00.0s
0.0 - 60.0 s
55
DC braking
edge/level selection
>A056 DCB
KIND LEVEL
EDGE(edge action) / LEVEL(level action)
56
DC braking power
(starting time)
>A057 DCB
STA-V 000%
0 - 100
%
(NOTE 3)
57
DC braking time
(starting time)
>A058 DCB
STA-T 00.0s
0.00 - 60.0 s
58
DC career
frequency
>A059 DCB
CARRIER 05.0kHz
0.5 -15.0 kHz (Derating)
(NOTE 4)
59
1
st
maximum
frequency limiter
>A061 LIMIT
HIGH 0000.00Hz
0.00
,
1
st
frequency lower limiter-maximum
frequency(Hz)
60
2
nd
maximum
frequency limiter
>A261 2LIMIT
HIGH 0000.00Hz
0.00
,
2
nd
frequency lower limiter-2
nd
setting
–maximum frequency(Hz)
61
1
st
minimum
frequency limiter
>A062 LIMIT
LOW 0000.00Hz
0.00
,
start frequency-maximum frequency(Hz)
62
2
nd
minimum
frequency limiter
>A262 2LIMIT
LOW 0000.00Hz
0.00
,
start frequency-2
nd
setting-maximum
frequency(Hz)
63 Jump
frequency1
>A063 JUMP
F1 0000.00Hz
0.00 - 400.00 Hz
64
Jump frequency
width 1
>A064 JUMP
W1 00.50Hz
0.00 - 10.00 Hz