(13) Over temperature (E 21)
Phenomena:
Temperature sensor which located close to IGBT inside ISPM shows a too high
temperature.
Cause:
Ventilator blocked. (for models which has ventilator.)
Remedy:
Check ventilator
Cause:
The frequency inverter does not get enough cooling air.
Remedy:
Check cabinet ventilation, air filters, and ventilation openings in the cabinet.
Way to Reset: A
(14) PTC error (E 35)
Phenomena:
Resistance of motor thermistor is high. This error can occur when you select
“PTC” function.
Cause:
Too much load of the motor.
Remedy:
Reduce the load, use bigger motor.
Cause:
Motor thermistor is not connected while PTC function is selected.
Remedy:
Disable PTC function when it is not used.
Cause:
Characteristics of the motor thermistor is not suitable. Frequency inverter gives
PTC error when the resistance value becomes more than 3k ohm +-10%.
Remedy:
Use motor which has suitable thermistor for the inverter.
Or change thermistor characteristics of the thermistor by debug mode.
Way to Reset:
A
Explanation of the way to reset.
A :
Make close the terminals between RS and P24 (CM1 only for Japanese version) on the I/O board, or
press “STOP/RESET” key of the operator.
3-6
Summary of Contents for SJ100 Series
Page 3: ...Revisions Revision history table No Revision contents Date of issue Manual No ⅰⅰ ...
Page 40: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ...End of page ...