Chapter 5
Chapter 5 – Troubleshooting
In general, the first step to troubleshooting should be to inspect the status LEDs on the SJ/L-EN board, in
addition to the inverter operator/keypad display. These will give valuable clues to the nature of the problem.
Refer to the description of the proper LED indications on page 11.
In addition, the inverter operator/keypad (if installed) will provide diagnostic information for certain types of
errors.
The error code for a communication error is:
E60
The following table summarizes possible error causes and remedies.
Code
Trip Name
Cause
Check
Remedy
Defective
connection
Connectors (plugs &
jacks), cable
Replace or repair; press
STOP/RESET on
inverter keypad, or
apply RST input
PC not powered up
or not connected to
inverter
That PC is powered on
and connected
Press STOP/RESET on
inverter keypad or apply
RST input
Network
configuration error
Verify proper Ethernet
setup of SJ/L-EN and
master device
Reconfigure incorrect
settings.
Board lockup
Check status LEDs
Press STOP/RESET key
on inverter, apply RST
input, or cycle power
E60
Ethernet
Communication
Error
Board defective
Check status LEDs
Replace SJ/L-EN
Refer also to the inverter’s Instruction Manual, Chapter 6, for additional troubleshooting assistance.
Page 19 of 36
Summary of Contents for SJ/L-EN Ethernet Communications Module
Page 2: ...NOTES ...
Page 4: ...Table of Contents NOTES Page 4 of 36 ...
Page 8: ...Chapter1 Page 8 of 36 NOTES ...
Page 12: ...Chapter2 Page 12 of 36 NOTES ...
Page 16: ...Chapter3 Page 16 of 36 NOTES ...
Page 18: ...Chapter 4 Page 18 of 36 NOTES ...
Page 20: ...Appendix Page 20 of 36 NOTES ...
Page 35: ...Index NOTES Page 35 of 36 ...
Page 36: ...December 2005 HAL1052 Hitachi America Ltd Tarrytown NY 10591 2005 www hitachi us inverters ...