Appendix
Page 22 of 36
F – Main Profile Functions
L200/SJ200
X10
0 – 4000
F001 4001 4002
Output frequency
setting(Hz) / PID
Setpoint (%)
L100/SJ100 X100
RO
0 – 36000
L200/SJ200 X100
-9999 –
300000
F002 4003 4004
Acceleration time
1
L100/SJ100 X10
R/W
0 – 30000
L200/SJ200 X100
-9999 –
300000
F202 4403 4404
Acceleration time
1, 2
nd
motor
SJ100 (NOT
L100)
X10
0 – 30000
L200/SJ200 X100
1 – 30000
-9999 –
300000
F003 4005 4006
Deceleration time
1
L100/SJ100 X10
R/W
0 – 30000
L200/SJ200 X100
-9999 –
300000
F203 4405 4406
Deceleration time
1, 2
nd
motor
SJ100 (NOT
L100)
X10
R/W
0 – 30000
F004
4007
4008
Keypad RUN key routing
X1
R/W
0 – 1
A – Standard Functions
A001 *
1
2
Frequency source setting
X1
R/W
0 – 5 *
A002 *
3
4
Run command source setting
X1
R/W
1 – 5 *
L200/SJ200
X1
30 – 400
SJ100
X100
5000 – 36000
A003 5 6
Base frequency
setting
L100 X1
R/W
50 – 360
L200/SJ200
X1
30 – 400
SJ100
X100
5000 – 36000
A203 405 406
Base frequency
setting, 2
nd
motor
L100 X1
R/W
50 – 360
L200/SJ200
X1
30 – 400
SJ100
X100
5000 – 36000
A004 7 8
Maximum
frequency setting
L100 X1
R/W
50 – 360
Summary of Contents for SJ/L-EN Ethernet Communications Module
Page 2: ...NOTES ...
Page 4: ...Table of Contents NOTES Page 4 of 36 ...
Page 8: ...Chapter1 Page 8 of 36 NOTES ...
Page 12: ...Chapter2 Page 12 of 36 NOTES ...
Page 16: ...Chapter3 Page 16 of 36 NOTES ...
Page 18: ...Chapter 4 Page 18 of 36 NOTES ...
Page 20: ...Appendix Page 20 of 36 NOTES ...
Page 35: ...Index NOTES Page 35 of 36 ...
Page 36: ...December 2005 HAL1052 Hitachi America Ltd Tarrytown NY 10591 2005 www hitachi us inverters ...