
44
8. Safety and Control Device Setting
The compressor is protected by the following devices and their combinations:
(1) High Pressure Switch: This switch cuts out the operation of the compressor when the discharge pressure
exceeds the setting.
(2) Crankcase Heater: This band type heater protects against oil foaming during cold starting, as it is energized
while the compressor is stopped.
Model
RAS-3.0~
3.5HNBRKQ1
RAS-4.0~
6.5HNBRKQ1
RAS-7.0~
8.0HNBRMQ1
RAS-10~
12HNBRMQ1
High Pressure Switch
Automatic Reset, Non-Adjustable
Automatic Reset, Non-Adjustable
Cut-Out
MPa
4.15
-0.05
-0.2
4.15
-0.05
-0.2
4.15
-0.05
-0.2
4.15
-0.05
-0.2
Cut-In
MPa
3.2
+0.15
-0.2
3.2
+0.15
-0.2
3.2
+0.15
-0.2
3.2
+0.15
-0.2
Breaker
A
32
40
25
40
Crankcase Heater
W
24
28
80
80
CCP Timer
Setting Time
Min
Non-Adjustable
3
Non-Adjustable
3
Non-Adjustable
3
Non-Adjustable
3