12
Model
Net Weight (kg)
Gross Weight (kg)
RAS-10HNBRMQ1
RAS-11HNBRMQ1
RAS-12HNBRMQ1
172
187
Do not place or leave any other objects (cables, tools) inside the outdoor unit or control board and verify
that nothing remains there prior to installation and test run. Ignoring the instructions can lead to damage and
fire incidents.
2.6 Factory Supplied Accessories
The accessories are packed with the outdoor unit, please check that in the package.
Accessory
Quantity
Remarks
Wire Clamp (big)
1
Only for RAS-
3.0~6.5HNBRKQ1
Wire Clamp (small)
3
Magnetic Ring (big)
2
Magnetic Ring (small)
1
Washer
4
Wire Clamp (big)
2
Only for RAS-
7.0~12HNBRMQ1
Pipe Adapter 1
1
Pipe Adapter 2
1
NOTE:
If any of these accessories are not packed in the unit, please contact your distributor.
3. Outdoor Unit Installation
3.1 Installation Location and Precautions
●
When installing the unit into:
●
A wall: Make sure the wall is strong enough to hold the weight of the unit. It may be necessary to
construct a strong wood or metal frame to provide added support.
●
A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can
cause dripping and water damage to wall and floors.
●
Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid and level
foundation for the unit to prevent water damage and abnormal vibration.
●
An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable wall for wind prevention (field-supplied).
●
A snowy area: Install the outdoor unit on a raised platform that is higher than drifting snow.
Provide snow roof for snow prevention (field-supplied).
●
Do not install the unit in the following places. Otherwise, it can result in an explosion, fire, deformation,
corrosion, or product failure.
● Explosive or flammable atmosphere.
● Where a fire, oil, steam, or powder can directly enter the unit, such as in close proximity or directly above
a kitchen stove.
●
Where oil (including machinery oil) may be present.
●
Where corrosive gases such as chlorine, bromine, or sulphide can accumulate, such as near a hot tub or
hot spring.
● Where dense, salt-laden airflow is heavy, such as in coastal regions.
WARNING
!