Figure 5.4 Electrical Wiring for RAS-7.0~12HNBRMQ1
NOTES:
●
Perform all the electrical work in accordance with the manual and in compliance with the local regulations and safety standards.
The electrical wiring should be applied by the qualified person.
●
The recommended electrical characteristics are calculated by the related safety standards. The environment temperature is less
than 40°C, the length of the power supply wire is no more than 15 meters. If the air conditioning is in an extreme environment,
please calculate the electrical characteristics again.
●
If the distribution box or pull box is adopted to the power supply for air conditioning, the size of the power supply wire should be
chosen according to the following table.
Total Ampacity
(A)
Power Supply Wiring
(mm
2
)
※
1:
If the total ampacity is over than
63A, the power supply wires must
not be connected in series.
I≤6
2.5
6<I≤10
2.5
10<I≤16
2.5
16<I≤25
4
25<I≤32
6
32<I≤40
10
40<I≤63
16
63<I
※
1
●
The power supply wire should be stranded copper with shielding by neoprene.
●
The transmission cables must be made up of the shielded twist pair cabling, and the shielded should be connected to the ground.
●
If the power supply wiring or the transmission cable is damaged, please turn off the power supply and contact the service dealer.
●
The ELB (Earth leakage breaker) must be installed to each power source of outdoor unit and indoor units. The distance between
the terminals of the ELB should be more than 3 mm.
●
When connect the power supply wirings, it is better that the ground wire should be longer than the live and neutral wires.