3 General data
3.3.2 RAS-(4-10)HRNME-AF
RAS Model
RAS-4HRNME-AF
RAS-5HRNME-AF
RAS-6HRNME-AF
RAS-8HRNME-AF
RAS-10HRNME-AF
Electrical power supply
3N~ 400V 50Hz
Color (Munsell code)
-
Natural gray (1.0Y8.5/0.5)
Sound pressure level
(night mode)
dB(A)
44(40)
46(42)
48(45)
52(50)
55(53)
Sound power level
dB(A)
65
67
69
74
77
Outside measure-
ments
Height
mm
1,380
1,380
1,380
1,650
1,650
Width
mm
950
950
950
1,100
1,100
Depth
mm
370
370
370
390
390
Net weight
kg
107
108
108
170
170
Refrigerant
-
R410A
Flow control
-
Microprocessor-controlled expansion valve
Compressor
-
DC inverter driven
Quantity
-
1
1
1
1
1
Power
kW
2.20
3.00
3.00
4.00
4.00
Heat exchanger
-
Multi-pass cross-finned tube
Condenser fan
-
Propeller fan
Quantity
-
1+1
1+1
1+1
1+1
1+1
Air flow rate
m³/
min
80
90
100
121
150
Power
W
70+70
70+70
70+70
170+120
170+120
Refrigerant pipe connection
-
Flare-nut connection (factory supplied)
Size
Liquid piping
mm
(in)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Ø12.70
(1/2”)
Gas piping
mm
(in)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Ø25.40
(1”)
Ø25.40
(1”)
Refrigerant charge
kg
3.90
4.00
4.00
7.3
7.8
Maximum current
A
7
11
13
13
17
Packaging measurements
m³
0.70
0.70
0.70
0.71
0.71
N O T E
The sound pressure level is based on following conditions:
• 1 meter from the frontal surface of the unit; 1.5 meters from floor level.
• Voltage of the power source is 400V.
The above data is measured in an anechoic chamber, so reflected sound should be taken into consideration