2 Features and benefits
TCGB0070 rev.3 - 04/2012
45
2
Three different possible water temperature set-point configuration modes for each zone
• OTC Points: Water target is selected by an Outside Temperature Compensated (OTC) control that is defined by 4
different points (Minimum and maximum water outlet temperature vs Minimum and maximum outdoor ambient tempe-
rature).
Outdoor ambient temperature (ºC)
Water temperature
set point ºC
(44) Tsh
n
h
(20) Tshr
n
l
Tah
n
l (-20)
Tah
n
h (20)
Water outlet temperature
set-point (ºC)
Outdoor ambient
temperature(ºC)
44
20
-20
20
•
OTC Gradient (Only for heating space): Water target is selected by an Outside Temperature Compensated (OTC)
control that is defined by a different gradient of the curve. The initial point of the curve is always 20ºC-20ºC (Water
outlet target 20ºC at outdoor ambient temperature of 20ºC).
W
ater outlet temperature set-point (ºC)
Outdoor ambient temperature (ºC)
Heat pump +
electric heater
or only boiler
Only boiler
(Bi-valent
combination)
• Fixed temperature: Water target value is defined by a fixed temperature set by the user.
Outdoor ambient temperature (ºC)
Water temperature
set point ºC
Tf
n
Water outlet temperatu-
re set-point (ºC)
Outdoor ambient
temperature(ºC)
35