![Hitachi RWM-(H)FSN3E Technical Catalogue Download Page 144](http://html.mh-extra.com/html/hitachi/rwm-h-fsn3e/rwm-h-fsn3e_technical-catalogue_2139430144.webp)
10 Electrical wiring
TCGB0070 rev.3 - 04/2012
144
10.3.2 Wire sizes
• Recommended minimum sizes for field provided wires
Model
Power supply
Max.
Current
(A)
Power
supply cable
size
Required
number
of wires
Transmi-
ting Cable
Size
Re-
quired
number
of wires
Actuator
cable size
Required
number
of wires
EN60335-1
EN60335-1
EN60335-1
RWM-2.0(H)FSN3E
1~ 230V 50Hz
16
4.0 mm²
2 + GND
0.75 mm
2
2 +
(*Shielded
cable)
0.75 mm
2
2 + GND
RWM-3.0(H)FSN3E
16
4.0 mm²
RWM-4.0(H)FSN3E
1~ 230V 50Hz
3N~ 400V 50Hz
32/11
6.0/2.5 mm²
2 + GND /
4 + GND
RWM-5.0(H)FSN3E
32/11
6.0/2.5 mm²
RWM-6.0(H)FSN3E
32/11
6.0/2.5 mm²
RWM-8.0(H)FSN3E
3N~ 400V 50Hz
17
4.0 mm²
4 + GND
RWM-10.0(H)FSN3E
17
4.0 mm²
RAS-2HVRN2
1~ 230V 50Hz
11
2.5 mm²
2 + GND
RAS-3HVRNME-AF
14
4.0 mm²
RAS-4HVRNME-AF
18
4.0 mm²
RAS-5HVRNME-AF
26
6.0 mm²
RAS-6HVRNME-AF
26
6.0 mm²
RAS-4HRNME-AF
3N~400V 50 Hz
7
2.5 mm²
4 + GND
RAS-5HRNME-AF
11
4.0 mm²
RAS-6HRNME-AF
13
4.0 mm²
RAS-8HRNME-AF
13
4.0 mm²
RAS-10HRNME-AF
17
4.0 mm²
N O T E
GND: Ground wire
•
Types of switches
Select the main switches in accordance with the following table:
Model
Power supply
Max. Current
(A)
CB (A)
ELB
(no. of poles/A/mA)
RWM-2.0(H)FSN3E
1~230V 50Hz
16
20
2/40/30
RWM-3.0(H)FSN3E
16
20
RWM-4.0(H)FSN3E
1~230V 50Hz
3N~400V 50Hz
32/11
32/15
2/40/30 - 4/40/30
RWM-5.0(H)FSN3E
32/11
32/15
RWM-6.0(H)FSN3E
32/11
32/15
RWM-8.0(H)FSN3E
3N~400V 50Hz
17
20
4/40/30
RWM-10.0(H)FSN3E
17
20
RAS-2HVRN2
1~230V 50Hz
11
16
2/40/30
RAS-3HVRNME-AF
14
25
RAS-4HVRNME-AF
18
25
RAS-5HVRNME-AF
26
32
RAS-6HVRNME-AF
26
32
RAS-4HRNME-AF
3N~400V 50 Hz
7
15
4/40/30
RAS-5HRNME-AF
11
20
RAS-6HRNME-AF
13
20
RAS-8HRNME-AF
13,2
20
RAS-10HRNME-AF
17,1
25
N O T E
CB: Circuit Breaker
ELB: Earth Leakage Breaker