17
/94
COMPONENTS DATA
17.3.
WATER COOLER
Model RCUE-AG1
40
50
60,70
80
100
120,140
150
180,200 240,270 300,330 360,400
Water Cooler
Brazed Type Plate Heat Exchanger
Type (Quantity)
A(1)
B(1)
C(1)
D(1)
E(1)
F(1)
B(1)
C(1)
F(2)
C(1)
F(3)
-See Table Below-
E(1)
F(1)
F(2)
SINGLE TYPE
DUAL TYPE
TYPE
A
B
C
D
E
F
REFRIGERANT CYCLE
40HP
50HP
60HP
80HP
100HP
120HP
Dimensions
Height (H)
mm
693
693
693
694
694
694
Width (W)
mm
243
243
243
304
304
304
Depth (D)
mm
186
225
269
294
372
460
Maximum Permissible Pressure
Refrigerant Side
Mpa
1.8
1.8
1.8
1.8
1.8
1.8
Water Side
MPa
1.0
1.0
1.0
1.0
1.0
1.0
Internal Volume
Refrigerant Side
Litre
11.2
13.9
16.8
2
×
11.8 2
×
15.1 2
×
18.9
Water Side
Litre
11.6
14.2
17.2
23.9
30.7
38.2
Material
Stainless Steel
Approval
PED (1)
NOTE:
Pressure equipment Directive (97/23/EC)
SINGLE TYPE
DUAL TYPE
Refrigerant Out
Water In
Water Out
Refrigerant In
No.1 Refrigerant Out
No.2 Refrigerant Out
No.1 Refrigerant In
No.2 Refrigerant In
Water In
Water Out
Refrigerant
Plates
Water
No.1 Refrigerant
Plates
Water
No.2 Refrigerant