10
/40
CONTROL SYSTEM
Standard Operation Sequence RCUE 360, 400AG1 (cont.)
Control Stage
Control Devices
Safety Devices
Shut Down
Main Power Switch
MI
-
-
-
-
-
-
-
-
ON
ON
ON
OFF
Operation Switch
PBS
-
-
-
-
-
-
-
OFF
ON
OFF
-
-
Load Up
-
-
!
!
!
!
!
-
-
-
-
-
Neutral
!
!
-
-
-
-
-
-
!
-
-
-
Controller
Load Down
-
-
-
-
-
-
-
-
-
-
-
-
No.1
CLS
OPN
OPN
OPN
OPN
OPN
OPN
CLS
CLS
CLS
CLS
CLS
No.2
CLS
CLS
OPN
OPN
OPN
OPN
OPN
CLS
CLS
CLS
CLS
CLS
No.3
CLS
CLS
CLS
OPN
OPN
OPN
OPN
CLS
CLS
CLS
CLS
CLS
No.4
CLS
CLS
CLS
CLS
OPN
OPN
OPN
CLS
CLS
CLS
CLS
CLS
No.5
CLS
CLS
CLS
CLS
CLS
OPN
OPN
CLS
CLS
CLS
CLS
CLS
Safety Devices
No.6
CLS
CLS
CLS
CLS
CLS
CLS
OPN
CLS
CLS
CLS
CLS
CLS
Chilled Water Pump
CPUE
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
Power Supply Indicator
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
Operation Indicator
ON
ON
ON
ON
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
Alarm Indicator
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
CH1
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
CH2
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
CH3
OFF
OFF
OFF
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
CH4
OFF
OFF
OFF
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
CH5
OFF
OFF
OFF
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
Oil Heater
CH6
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
MC1
DLT
DLT
(ULD)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
(ULD)
OFF
OFF
OFF
25~99%
25~99%
MC2
DLT
DLT
DLT
(ULD)
(ULD)
OFF
OFF
OFF
OFF
OFF
OFF
(ULD)
OFF
OFF
OFF
25~99%
25~99%
25~99%
MC3
DLT
DLT
DLT
DLT
(ULD)
(ULD)
(ULD)
OFF
OFF
OFF
OFF
OFF
(ULD)
OFF
OFF
OFF
25~99%
25~99% 25~99%
25~99%
MC4
DLT
DLT
DLT
DLT
DLT
(ULD)
(ULD)
(ULD)
(ULD)
OFF
OFF
OFF
OFF
(ULD)
OFF
OFF
OFF
25~99%
25~99% 25~99% 25~99%
25~99%
MC5
DLT
DLT
DLT
DLT
DLT
DLT
(ULD)
(ULD)
(ULD)
(ULD)
(ULD)
OFF
OFF
OFF
(ULD)
OFF
OFF
OFF
25~99%
25~99% 25~99% 25~99%
25~99%
25~99%
MC6
DLT
DLT
DLT
DLT
DLT
DLT
DLT
(ULD)
(ULD)
(ULD)
(ULD)
(ULD)
(ULD)
OFF
OFF
(ULD)
OFF
OFF
OFF
Compressor Motor
25~99%
25~99% 25~99% 25~99%
25~99%
25~99%
25~99%
MF11~14
ON (Q'ty Depends on "Fan Cycling Control")
OFF
OFF
ON
OFF
OFF
OFF
MF21~24
ON (Q'ty Depends on "Fan Cycling Control")
OFF
OFF
ON
OFF
OFF
OFF
MF31~34
ON (Q'ty Depends on "Fan Cycling Control")
OFF
OFF
ON
OFF
OFF
OFF
MF41~44
ON (Q'ty Depends on "Fan Cycling Control")
OFF
OFF
ON
OFF
OFF
OFF
MF51~54
ON (Q'ty Depends on "Fan Cycling Control")
OFF
OFF
ON
OFF
OFF
OFF
Fan Motor
MF61~64
ON (Q'ty Depends on "Fan Cycling Control")
OFF
OFF
ON
OFF
OFF
OFF
SV11
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV12
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV13
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV21
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV22
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV23
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV31
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV32
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV33
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV41
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV42
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV43
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV51
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV52
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV53
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV61
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV62
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Solenoid Valve
SV63
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
Time Schedule
CLS Close
OPN: Open
STA: Star
DLT Delta
10sec.
The Compressor which started finally
will be restarted first.
ULD: Unload
FLD: Full Load
!
: Changing Compressor Load
!
: Keeping Compressor Load