GENERAL SPECIFICATIONS
13
/55
13.
GENERAL SPECIFICATIONS
13.1.
GENERAL DATA
Model (R407C)
RCUE40AG1
RCUE50AG1
RCUE60AG1
RCUE70AG1
Cooling Capacity
KW
108
126
156
178
Total Power Input
KW
41,1
48,1
59,3
68,4
COP
-
2,63
2,62
2,63
2,60
Height
Mm
2.430
2.430
2.430
2,430
Width
Mm
1.800
1.800
1.800
1,800
Outer Dimension
Depth
Mm
2.050
2.050
2.050
2,050
Cabinet Colour
Natural Gray
Net Weight
Kg
1.530
1.590
1.760
1.780
Compressor Type
-
Semi-Hermetic Screw Type
Model
-
4005SC-Z
4005SC-Z
5005SC-Z
6005SC-Z
Quantity
-
1
1
1
1
Oil Heater
W
150
150
150
150
-
Continuous Capacity Control
Capacity Control
%
33~100
33~100
25~100
25~100
Water Cooler Type
-
Brazing Plate Type
Condenser Type
-
Multi-Pass Cross Finned Tube
Fan Motor (Pole)
KW
0.4 (6)
0.4 (6)
0.4 (6)
0.4 (6)
Quantity
-
4
4
4
4
Refrigerant Type
R407C(Factory Charged)
Flow Control
-
Thermal Expansion Valve
Number of Independent
Circuits
-
1
1
1
1
Oil Type
-
CASTROL ICEMATIC SW220HT (Ester)
Water Pipe Connection
Inch
3" Victaulic ( 1 x INLET / 1 X OUTLET )
Control System
-
Micro-Processor Control
Chilled Water Outlet Temperature
C
5~15
Condenser Air Inlet Temperature
C
5~43 (Option:-15~43)
Permissible Water Pressure Max.
MPa
1.0
Safety and Protection Devices
-
Reverse Phase Protection Device, Fuse and Thermal Relay for Compressor,
Internal Thermostat for Compressor, Compressor Oil Heater,
Fuse and internal Thermostat for Fan Motor, Control Circuit Fuse,
High Pressure Switch, Low Pressure Control, High Pressure Relief Valve,
Discharge Gas Temperature Control, Suction Gas Temperature Control, Freeze
Proctection Control and Compressor Operation Hour Meter
Power Supply
3~,N/380-415V/50Hz
NOTE:
The nominal cooling capacities are based on the European Standard EN12055.
- Chilled Water Inlet/Outlet Temperature: 12/7 °C
- Condenser Inlet Air Temperature: 35 °C
- Cooling Capacity and total power input data at 40~43ºC are available at distributor side