DEFROST
Reversing valve defrost system is employed: it consists of balancing period reversing cycle period balancing period.
When all the following conditions are established defrost is executed:
Normal operation
Defrost start condition
(1)
Defrost inhibit period linked to outdoor temperature has passed.
Heat exchange temperature is within defrost range specified by outdoor temperature and heat exchange temperature.
1
3
2
If any one of the following conditions is established, defrost is released:
Defrost release condition
(2)
Outputs during defrost
(3)
Indoor defrost request: Transmitted to all units being operated in heating mode.
Electric expansion valve
Unit being stopped : [FULL CLOSE] 30 seconds after balancing period has passed [FULL CLOSE] during
reversing cycle period [PCLOSH$] 15 seconds before balancing period is finished
Unit being operated : [DFCTPS] 30 seconds before balancing period is finished Synchronized with step-up
of rotation speed of compressor, opened by [DFSPPS] pulses and reaches MAX opening
degree [DEFSMX] when rotation speed of compressor reaches [DEFMAX].
Compressor : Balancing period for [TDF414] seconds Starting of reversing cycle period by [SDRCT2] min
-1
for
Released by condition 1 or 2 during reversing cycle period: [TDF415] Shifted to balancing period.
[TSKTM2] seconds Accelerating by [DFSTEP]min
-1
/[TDFSPT] seconds in remaining reversing cycle
period until defrost MAX speed [DEFMAX] is reached Balancing period for [TDF415] seconds
Released by condition 1 during balancing period: When remaining balancing period has elapsed, returned to initial
condition (ASTUS=0).
above graph is showing the ideal value by micon program.
Heat exchange temperature returns (heat exchange temperarure
≥
DEFOFF).
Defrost max time of 12 minutes has elapsed.
1
2
RAM-55QH4, RAM-65QH4 DEFROST TEMPERATURE
OUTDOOR (˚C)
-20
-10
10
20
0
0
-10
10
-20
20
HEA
T EXCHANGER (
˚C)
DEFROST
START
TEMPERATURE
DEFROST END
TEMPERATURE
Summary of Contents for RAM-55QH4
Page 31: ... 30 CAPACITY DIAGRAM RELATED TO THE PIPING LENGTH MODEL RAM 65QH4 ...
Page 37: ...CIRCUIT DIAGRAM MODEL RAM 55QH4 39 L C023 C022 C002 C001 C025 C024 N ...
Page 38: ...CIRCUIT DIAGRAM MODEL RAM 65QH4 41 L C023 C022 C002 C001 C025 C024 N ...
Page 41: ... 45 ...
Page 47: ... 53 Outdoortemperature STAROTP_C TSKTM1_C1 Outdoortemperature STAROTP_C TSKTM1_C2 ...
Page 48: ... 55 ...
Page 49: ... 57 ...
Page 50: ... 59 ...
Page 51: ... 61 ...
Page 69: ... 79 5A ...
Page 76: ... 86 ...
Page 92: ... 105 ...
Page 93: ... 106 ...
Page 99: ... 112 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Page 100: ... 113 ...
Page 101: ... 114 ...
Page 103: ... 116 three three inlet 3 Cut off the three pipes at the side and bottom of Reversing valve ...
Page 104: ... 117 ELECTRIC EXPANSION VALVE PIPE THERMISTOR POSITION CHARTS MODEL RAM 55QH4 MODEL RAM 65QH4 ...
Page 109: ...HITACHI PM NO 0217E Printed in Malaysia RAM 55QH4 RAM 65QH4 ...