HOW TO OPERATE USING THE SERVICE SWITCH THE OUTDOOR UNIT
MODEL RAM-52QH5 , RAM-53QH5
1. Turn the Power switch off and then turn on again.
2. Remove the electrical parts cover.
3. Press the service switch for one second or more (wait for at least 30 seconds after turning the power source switch
on).
Open the upper cover
Service switch
(forced-cooling mode is set by
pressing for 1 second or
more, and stopped by pressing
again.)
(Cautions)
(1) If interface signal (35V DC) terminals C and D are not connected when the outdoor unit service switch is used for
checking, the outdoor unit defects indicator (LD304) will blink to indicate communication error.
(2) If you do this with the compressor connector in a removed state, LD301 will blink four times, and the unit will not
work.
HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
Be sure to return the service switch to "normal" after checking with service operation is completed.
1. Connect the large dia. pipe side and small dia. pipe side service valves using a pipe.
Connect the small diameter
service value and the large
diameter service valve using
the reducing union and copper
pipe as shown on the right.
Charge refrigerant of 300g af-
ter vacuuming ( 1)
(1) Reducing union
2/8" (6.35mm)
3/8" (9.52mm)
(2) Copper pipe (2/8" and 3/8")
Parts to be prepared
Do not operate for 5 minutes or
more
The operation method is the same as "How to operate using the connector to servicing the outdoor unit"
1 The charging amount of 300g is equivalent to the load in normal operation.
Never operate the unit
in this state for more
than 5 minutes.
Summary of Contents for RAM-52QH5
Page 16: ... 15 MODEL RAM 52QH5 ...
Page 17: ... 16 MODEL RAM 53QH5 ...
Page 30: ... 29 CAPACITY DIAGRAM RELATED TO THE PIPING LENGTH MODEL RAM 53QH5 ...
Page 36: ...CIRCUIT DIAGRAM MODEL RAM 52QH5 39 L C023 C022 C002 C001 C025 C024 N ...
Page 37: ...CIRCUIT DIAGRAM MODEL RAM 53QH5 41 L C023 C022 C002 C001 C025 C024 N ...
Page 40: ... 45 ...
Page 42: ... 49 Outdoortemperature STAROTP_C TSKTM1_C1 Outdoortemperature STAROTP_C TSKTM1_C2 ...
Page 43: ... 51 ...
Page 44: ... 53 ...
Page 45: ... 55 ...
Page 46: ... 57 ...
Page 58: ... 69 REFRIGERATING CYCLE DIAGRAM RAM 52QH5 ...
Page 59: ... 70 REFRIGERATING CYCLE DIAGRAM RAM 52QH5 ...
Page 60: ... 71 REFRIGERATING CYCLE DIAGRAM RAM 53QH5 ...
Page 61: ... 72 REFRIGERATING CYCLE DIAGRAM RAM 53QH5 ...
Page 64: ... 75 5A ...
Page 67: ... 78 3 System power Module Circuit ...
Page 71: ... 82 ...
Page 72: ... 83 5 Reversing valve control circuit Fig 5 1 ...
Page 87: ... 101 ...
Page 88: ... 102 ...
Page 94: ... 108 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Page 95: ... 109 ...
Page 96: ... 110 ...
Page 98: ... 112 three three inlet 3 Cut off the three pipes at the side and bottom of Reversing valve ...
Page 99: ... 113 ELECTRIC EXPANSION VALVE PIPE THERMISTOR POSITION CHARTS MODEL RAM 53QH5 MODEL RAM 52QH5 ...
Page 104: ...HITACHI PM NO 0428E Printed in Malaysia RAM 52QH5 RAM 53QH5 ...