– 66 –
FORCED COOLING
[Execution condition]
In order to accumulate refrigerant, units operate in cooling cycle.
Execution condition and operation status are shown below.
With neither indoor unit 1, 2 and 3 not operated, when forced cooling switch is turned ON, forced cooling will be performed.
[Operation status]
Outdoor unit fan: Fixed in LO.
[Note]
During forced cooling, if failure occurs in outdoor unit, thermostat is turned off. However, it is not counted.
The following shows the operation state of forced cooling.
Since rotation speed of compressor is fixed in 3000min
-1
during forced cooling, compressor fixed speed control at start is
not performed.
Expansion valve/reversing valve : Set in normal conditions.
Compressor rotation speed: Fixed in 3000min
-1
.
Always operation status of indoor units are monitored and forced cooling is inhibited when operation of any unit is detected.
Power
Heating output
Service switch
Cooling output
Outdoor fan
Turns on
for Cooling
Operation
Power
Compressor
rotation speed
In-rush Prevention
Compressor
P
o
w
er rela
y
Electric e
xpansion valv
e
Main microcomputer
R
e
ve
rsing
valv
e
Unit 1
Unit 2
Unit 3
Unit 1
Unit 2
Unit 3
Hold
Hold
Hold
Approx.100ms
100ms
1sec.
1sec.
1sec.
520
480
0
520
480
0
520
480
0
TSKTM1_C and PSTARTC2$ are EEPROM da ta.
Hold 500ms
Hold 500ms
Hold 500ms
31.25PPS
PSTARTC2$
PSTARTC2$
PSTARTC2$
Initialization
finished
[Outdoor temperature < 40˚C]
[Outdoor temperature < 40˚C]
[Outdoor temperature < 40˚C]
Initialization
finished
< TD control + N compensation + Diving control >
< TD control + N compensation + Diving control >
< TD control + N compensation + Diving control >
TSKTMI_C1
Outdoor temperature
≥
STARCTP_C
TSKTMI_C2
Outdoor temperature
≤
STARCTP_C
Forced cooling request
Forced cooling request
Forced cooling request
Balancing request
Balancing request
Balancing request
Balancing period 3min.
Lo
3000min
-1
15sec. +sub
30sec.
80sec.
MODEL RAM-53QH5
Summary of Contents for RAM-52QH5
Page 16: ... 15 MODEL RAM 52QH5 ...
Page 17: ... 16 MODEL RAM 53QH5 ...
Page 30: ... 29 CAPACITY DIAGRAM RELATED TO THE PIPING LENGTH MODEL RAM 53QH5 ...
Page 36: ...CIRCUIT DIAGRAM MODEL RAM 52QH5 39 L C023 C022 C002 C001 C025 C024 N ...
Page 37: ...CIRCUIT DIAGRAM MODEL RAM 53QH5 41 L C023 C022 C002 C001 C025 C024 N ...
Page 40: ... 45 ...
Page 42: ... 49 Outdoortemperature STAROTP_C TSKTM1_C1 Outdoortemperature STAROTP_C TSKTM1_C2 ...
Page 43: ... 51 ...
Page 44: ... 53 ...
Page 45: ... 55 ...
Page 46: ... 57 ...
Page 58: ... 69 REFRIGERATING CYCLE DIAGRAM RAM 52QH5 ...
Page 59: ... 70 REFRIGERATING CYCLE DIAGRAM RAM 52QH5 ...
Page 60: ... 71 REFRIGERATING CYCLE DIAGRAM RAM 53QH5 ...
Page 61: ... 72 REFRIGERATING CYCLE DIAGRAM RAM 53QH5 ...
Page 64: ... 75 5A ...
Page 67: ... 78 3 System power Module Circuit ...
Page 71: ... 82 ...
Page 72: ... 83 5 Reversing valve control circuit Fig 5 1 ...
Page 87: ... 101 ...
Page 88: ... 102 ...
Page 94: ... 108 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Page 95: ... 109 ...
Page 96: ... 110 ...
Page 98: ... 112 three three inlet 3 Cut off the three pipes at the side and bottom of Reversing valve ...
Page 99: ... 113 ELECTRIC EXPANSION VALVE PIPE THERMISTOR POSITION CHARTS MODEL RAM 53QH5 MODEL RAM 52QH5 ...
Page 104: ...HITACHI PM NO 0428E Printed in Malaysia RAM 52QH5 RAM 53QH5 ...