5. Reversing valve control circuit
●
By reversing valve control circuit you can switch reversing valve ON/OFF (Heating ON) according to instruction
from indoor microcomputer and depending on operation condition.
Voltage at each point in each operation condition is approximately as shown below when measured by tester.
(When collector voltage of Q831 is measured)
3
1
24
0V
Fig. 5 1
D831
CN2
Q831
DC voltmeter
or tester
Reversing
valve
R832
R833
IC8
Micro
Computer
PQ831
12V
35V
R831
V
Operation condition
Collector voltage of Q831
Cooling
Heating
Dehumidifying
General operation of Cooling
In normal heating operation
MAX. rotation speed instructed
by indoor microcomputer after
defrost is completed
Defrosting
Sensor dry
About 35V
About 0.8V
About 0.8V
About 35V
About 35V
Table 5-1