– 82 –
Remarks:
When this unit were mean to be connected to mul
Ɵ
outdoor unit system, below diagnosis table shall be use.
If LD301 lit and at the same
Ɵ
me LD302 blinks in a number of
Ɵ
mes, this indicates thermistor faulty.
TIMER
LAMP
BLINKING
LD302
BLINKING
WIRELESS
REMOCON
CODE
WIRED
REMOCON
CODE
MEANING
DETAILS
MAIN CHECK POINT
4
Ɵ
mes
1
Ɵ
me
071
01
OVERHEAT THERMISTOR
4
Ɵ
mes
2
Ɵ
mes
072
01
DEFROST THERMISTOR
4
Ɵ
mes
3
Ɵ
mes
073
01
OUTDOOR TEMPERATURE THERMISTOR
4
Ɵ
mes
4
Ɵ
mes
074
01
NARROW PIPE THERMISTOR
(INDOOR NO.1)
4
Ɵ
mes
5
Ɵ
mes
075
01
WIDE PIPE THERMISTOR
(INDOOR NO.1)
4
Ɵ
mes
6
Ɵ
mes
076
01
NARROW PIPE THERMISTOR
(INDOOR NO.2)
4
Ɵ
mes
7
Ɵ
mes
077
01
WIDE PIPE THERMISTOR
(INDOOR NO.2)
4
Ɵ
mes
8
Ɵ
mes
078
01
NARROW PIPE THERMISTOR
(INDOOR NO.3)
4
Ɵ
mes
9
Ɵ
mes
079
01
WIDE PIPE THERMISTOR
(INDOOR NO.3)
4
Ɵ
mes
10
Ɵ
mes
080
01
NARROW PIPE THERMISTOR
(INDOOR NO.4)
4
Ɵ
mes
11
Ɵ
mes
081
01
WIDE PIPE THERMISTOR
(INDOOR NO.4)
4
Ɵ
mes
12
Ɵ
mes
082
01
NARROW PIPE THERMISTOR
(INDOOR NO.5)
4
Ɵ
mes
13
Ɵ
mes
083
01
WIDE PIPE THERMISTOR
(INDOOR NO.5)
If LD304 blinks, the number of blinks indicates a communica
Ɵ
on error with the corresponding indoor unit connec
Ɵ
on.
Detail as per below table.
TIMER
LAMP
BLINKING
LD304
BLINKING
WIRELESS
REMOCON
CODE
WIRED
REMOCON
CODE
MEANING
DETAILS
MAIN CHECK POINT
-
1
Ɵ
me
COMMUNICATION ERROR BETWEEN OUTDOOR AND
INDOOR UNIT NO.1
-
2
Ɵ
mes
COMMUNICATION ERROR BETWEEN OUTDOOR AND
INDOOR UNIT NO.2
-
3
Ɵ
mes
COMMUNICATION ERROR BETWEEN OUTDOOR AND
INDOOR UNIT NO.3
-
4
Ɵ
mes
COMMUNICATION ERROR BETWEEN OUTDOOR AND
INDOOR UNIT NO.4
Note : This communica
Ɵ
on error diagnosis table only applicable for 2 rooms un
Ɵ
l 4 rooms mul
Ɵ
system model.
Other shall refer to diagnosis table on the electrical cover or inside outdoor service manual.
THERMISTOR IS OPENED OR SHORTED
1. THERMISTOR
2. CONNECTION OF THERMISTOR IS FAULTY
3. THERMISTOR CIRCUIT
OUTDOOR
OUTDOOR
009
01
EVEN WHEN INDOOR UNIT IS NOT
CONNECTED, IT BLINKS SIMILARLY.
(NOT MALFUNCTION)
1. INDOOR TO OUTDOOR C-D LINE CABLE
NOT CONNECTED PROPERLY.
2. COMMUNICATION CIRCUIT DAMAGED.
3. DC35V POWER SUPPLY DAMAGED.
4. EFFECT OF EXTERNAL NOISE TO C-D LINE
CABLE.
Summary of Contents for RAM-36NP2A
Page 45: ... 43 MODEL RAI 25RPA RAI 35RPA RAI 50RPA WIRING DIAGRAM INDOOR UNIT ...
Page 46: ...Remote Control CIRCUIT DIAGRAM 45 ...
Page 47: ...CIRCUIT DIAGRAM MODEL RAI 25RPA RAI 35RPA RAI 50RPA 47 ...
Page 48: ... 49 ...
Page 49: ... 51 ...
Page 52: ... 57 ...
Page 54: ... 61 ...
Page 56: ... 65 ...
Page 57: ... 67 ...
Page 62: ... 73 ...
Page 69: ... 80 ...
Page 70: ... 81 ...
Page 72: ... 83 1 Power does not come on no operation CHECKING INDOOR UNIT ELECTRICAL PARTS ...
Page 74: ... 85 ...
Page 75: ... 86 ...
Page 76: ... 87 HOW TO CHANGE THE SHIFT VALUE for SETTING TEMPERATURE USING WIRED REMOTE CONTROLLER ...
Page 77: ... 88 ...
Page 78: ... 89 ...
Page 79: ... 90 ...
Page 80: ... 91 CHECKING THE REMOTE CONTROLLER ...
Page 81: ... 92 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAI 25RPA RAI 35RPA RAI 50RPA ...
Page 85: ... 96 MODEL RAI ECPP PANEL ...
Page 87: ...HITACHI PM NO 0530E Printed in Malaysia RAI 25RPA RAI 35RPA RAI 50RPA ...