– 63 –
Notes:
(1) Condition for entering into Hot Dashed mode. When fan set to “Hi” or “Auto mode” and i) Indoor temperature is lower than 18°C, and ii) outdoor temperature is lower than
10°C, and iii) Temperature difference between indoor temperature and set temperature has a corresponding compressor rpm larger than WMAX.
(2) Hot Dashed will release when i) Room temperature has achieved the set tempe SFTDSW. ii) Thermo off.
(3) During Hot Dashed operation, thermo off temperature is set temperature (with shift value) +4°C. After thermo off, operation continue in Fuzzy control mode.
(4) Compressor minimum “ON” time and “OFF” time is 3 minutes.
(5) During normal heating mode, compressor maximum rpm WMAX will maintain for 120 minutes if indoor temperature is higher than 18°C. No time limit constrain if indoor
temperature is lower than 18°C and outdoor temperature is lower than 2°C.
(6) During Hotkeep or Defrost mode, indoor operation lamp will blink at interval of 3 seconds “ON” and 0.5 second “OFF”.
(7) When heating mode starts, it will enter into Hotkeep mode if indoor heat exchanger temperature is lower than YNEOF + 0.33°C.
(8) When fan is set to “Med” or “Lo”, compressor rpm will be limited to WBEMAX.
(9) In “Ultra-Lo” fan mode, if indoor temperature is lower than 18°C, indoor fan will stop. If indoor temperature is higher than 18°C + 0.33°C, fan will continue in “Ultra-Lo” mode.
During Hotkeep or Defrost mode, fan will continue in “Ultra-Lo” mode.
(10) During Hot Dashed or outdoor temperature is lower than –5°C, compressor rpm is WMAX2.
(11) During Hot Dashed, when room temperature reaches set tempe SFTDSW compressor rpm is actual rpm x DWNRATEW.
Summary of Contents for RAM-36NP2A
Page 45: ... 43 MODEL RAI 25RPA RAI 35RPA RAI 50RPA WIRING DIAGRAM INDOOR UNIT ...
Page 46: ...Remote Control CIRCUIT DIAGRAM 45 ...
Page 47: ...CIRCUIT DIAGRAM MODEL RAI 25RPA RAI 35RPA RAI 50RPA 47 ...
Page 48: ... 49 ...
Page 49: ... 51 ...
Page 52: ... 57 ...
Page 54: ... 61 ...
Page 56: ... 65 ...
Page 57: ... 67 ...
Page 62: ... 73 ...
Page 69: ... 80 ...
Page 70: ... 81 ...
Page 72: ... 83 1 Power does not come on no operation CHECKING INDOOR UNIT ELECTRICAL PARTS ...
Page 74: ... 85 ...
Page 75: ... 86 ...
Page 76: ... 87 HOW TO CHANGE THE SHIFT VALUE for SETTING TEMPERATURE USING WIRED REMOTE CONTROLLER ...
Page 77: ... 88 ...
Page 78: ... 89 ...
Page 79: ... 90 ...
Page 80: ... 91 CHECKING THE REMOTE CONTROLLER ...
Page 81: ... 92 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAI 25RPA RAI 35RPA RAI 50RPA ...
Page 85: ... 96 MODEL RAI ECPP PANEL ...
Page 87: ...HITACHI PM NO 0530E Printed in Malaysia RAI 25RPA RAI 35RPA RAI 50RPA ...