– 106 –
3. Only indoor fan does not operate (other is normal)
Can the fan be stopped by
remote control?
Are pulse signals output at
microcomputer pin
15
-
18
when auto
swing is turned on in the fan mode?
Is a voltage over 15V or below 10V
being generated on the 12V line
Replace IC111
Replace the microcomputer
Check IC711. If it is normal,
replace the air deflector motor.
Replace the microcomputer.
Replace the indoor fan motor.
Replace the microcomputer.
Perform final operation check.
Perform final operation check.
The microcomputer fan PWM
output (pin) is “Hi”
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
No
No
Yes
No
No
Set to the “Hi” fan mode.
The operation lamp lights once and goes out in 5-10 seconds.
Disconnect CN10 and set to the fan mode again.
Replace the indoor fan motor.
The operation lamps lights once and goes out in 5-10 seconds.
Check to see if shorting etc. has occurred
in the P.W.B pattern
Check to see if the indoor fan is touching
the chassis, etc. If it does repair
Can the indoor fan be lightly turned by hand?
(Switch of main power before check)
4. Air deflector does not move (others are normal)
5. All systems stop from several seconds to several minutes after operation is started (all indicators
are also off)
Summary of Contents for RAC-50NH5
Page 32: ... 30 CONSTRUCTION AND DIMENSIONAL DIAGRAM ...
Page 33: ... 31 CONSTRUCTION AND DIMENSIONAL DIAGRAM FOR OUTDOOR MODEL RAC 50NH5 ...
Page 38: ... 39 ...
Page 39: ... 41 ...
Page 40: ... 43 ...
Page 41: ... 44 MODEL RAK 50NH5 RECEIVING P W B MARKING ON P W B COMPONENT SIDE SOLDERING SIDE ...
Page 42: ... 45 MAIN P W B ...
Page 43: ... 47 ...
Page 44: ... 49 ...
Page 46: ... 53 ...
Page 47: ... 55 ...
Page 48: ... 57 ...
Page 49: ... 59 ...
Page 50: ... 61 ...
Page 52: ... 64 N O I T C N U F G N I W S O T U A ...
Page 53: ... 65 RAK 50NH5 ...
Page 56: ... 68 ...
Page 58: ... 70 ...
Page 59: ... 71 ...
Page 60: ... 72 ...
Page 61: ... 73 ...
Page 62: ... 74 ...
Page 63: ... 75 ...
Page 64: ... 76 ...
Page 65: ... 77 ...
Page 66: ... 78 ...
Page 67: ... 79 ...
Page 68: ... 80 ...
Page 70: ... 82 ...
Page 71: ... 83 6 Rotor magnetic pole position detection circuit Ð Ð Ð Ð ...
Page 72: ... 84 7 Drive Circuit ...
Page 73: ... 85 Low speed rotation mode High speed rotation mode ...
Page 74: ... 86 8 HIC and Peripheral Circuits ...
Page 75: ... 87 ...
Page 76: ... 88 1 ...
Page 77: ... 89 2 5 ...
Page 78: ... 90 Ð Ð Ð Ð ...
Page 79: ... 91 9 Temperature Detection Circuit ...
Page 80: ... 92 10 Reset Circuit Ò Ó Ò Ó Ò Ó Ð ...
Page 81: ... 93 Ð 11 Outdoor DC Fan Motor control circuit Ð Ð ...
Page 83: ... 95 12 Power Factor Control Circuit ...
Page 84: ... 96 ...
Page 86: ... 98 OTHERS Q15 A15 Q16 A16 Q17 A17 Q18 A18 Q19 A19 ...
Page 87: ... 99 TROUBLE SHOOTING Model RAK 50NH5 RAC 50NH5 M ...
Page 91: ... 103 SELF DIAGNOSIS LIGHTING MODE ...
Page 97: ... 109 ...
Page 99: ... 111 ...
Page 100: ... 112 ...
Page 109: ... 121 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAK 50NH5 ...
Page 111: ... 123 ...
Page 113: ...RAK 50NH5 RAC 50NH5 HITACHI PM NO 0302E Printed in Malaysia ...