– 94 –
< Reference >
●
When operation stop with LD301 blinks 12 times, it may be caused by faulty DC fan motor.
●
In this case, please check CN6 and CN12 connection first. It makes Fan Motor Lock also if those
connectors are in misconnection.
●
DC Fan Motor has broken when 2A Fuse was burned. Please replace both DC Fan Motor and 2A Fuse
together.
●
It will makes ÒFan Lock StopÓ when something has disturb the Fan rotation by inserting materials into
propeller fan or ice has growing inside of outdoor unit by snowing.
●
It may make ÒFan Lock StopÓ by strong wind (ex. 17m/sec or above) against the Fan rotation. In this case,
unit will be restart again after a while.
●
In case of ÒFan Lock StopÓ even though the DC Fan Motor is rotating correctly, the possible casue is
Fan Motor problem or PQ102 on board or control board problem. Stop after the Fan motor runs 2 minutes,
Fan Motor may be broken.
< Caution >
●
Please take care for the electrical shock by high voltage of DC Fan Motor power source which is common
with compressor when you are servicing this unit.
●
You can not confirm the coil and wiring of Motor due to the built in control circuit in Fan Motor.
Summary of Contents for RAC-50NH5
Page 32: ... 30 CONSTRUCTION AND DIMENSIONAL DIAGRAM ...
Page 33: ... 31 CONSTRUCTION AND DIMENSIONAL DIAGRAM FOR OUTDOOR MODEL RAC 50NH5 ...
Page 38: ... 39 ...
Page 39: ... 41 ...
Page 40: ... 43 ...
Page 41: ... 44 MODEL RAK 50NH5 RECEIVING P W B MARKING ON P W B COMPONENT SIDE SOLDERING SIDE ...
Page 42: ... 45 MAIN P W B ...
Page 43: ... 47 ...
Page 44: ... 49 ...
Page 46: ... 53 ...
Page 47: ... 55 ...
Page 48: ... 57 ...
Page 49: ... 59 ...
Page 50: ... 61 ...
Page 52: ... 64 N O I T C N U F G N I W S O T U A ...
Page 53: ... 65 RAK 50NH5 ...
Page 56: ... 68 ...
Page 58: ... 70 ...
Page 59: ... 71 ...
Page 60: ... 72 ...
Page 61: ... 73 ...
Page 62: ... 74 ...
Page 63: ... 75 ...
Page 64: ... 76 ...
Page 65: ... 77 ...
Page 66: ... 78 ...
Page 67: ... 79 ...
Page 68: ... 80 ...
Page 70: ... 82 ...
Page 71: ... 83 6 Rotor magnetic pole position detection circuit Ð Ð Ð Ð ...
Page 72: ... 84 7 Drive Circuit ...
Page 73: ... 85 Low speed rotation mode High speed rotation mode ...
Page 74: ... 86 8 HIC and Peripheral Circuits ...
Page 75: ... 87 ...
Page 76: ... 88 1 ...
Page 77: ... 89 2 5 ...
Page 78: ... 90 Ð Ð Ð Ð ...
Page 79: ... 91 9 Temperature Detection Circuit ...
Page 80: ... 92 10 Reset Circuit Ò Ó Ò Ó Ò Ó Ð ...
Page 81: ... 93 Ð 11 Outdoor DC Fan Motor control circuit Ð Ð ...
Page 83: ... 95 12 Power Factor Control Circuit ...
Page 84: ... 96 ...
Page 86: ... 98 OTHERS Q15 A15 Q16 A16 Q17 A17 Q18 A18 Q19 A19 ...
Page 87: ... 99 TROUBLE SHOOTING Model RAK 50NH5 RAC 50NH5 M ...
Page 91: ... 103 SELF DIAGNOSIS LIGHTING MODE ...
Page 97: ... 109 ...
Page 99: ... 111 ...
Page 100: ... 112 ...
Page 109: ... 121 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAK 50NH5 ...
Page 111: ... 123 ...
Page 113: ...RAK 50NH5 RAC 50NH5 HITACHI PM NO 0302E Printed in Malaysia ...