– 101 –
CHECKING THE INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING CYCLE
Model RAC-50NH5
Does the timer lamp on the indoor unit blink?
Is the compressor in the outdoor unit operating?
Does the operation lamp on the indoor unit
start to light or blink?
Remove the outdoor unit cover and
electrical parts cover, and check
self-diagnosis lamp LD301
Does LD301 blink one time ?
* Repeats 0.25-second on and
2-second off.
Blinking other than
one time
One-time blinking
Yes
Yes
Yes
Yes
No
No
No
Normal
No
No
Timer
lamp
Press the service switch for 1 sec.
Does the compressor operate?
(After checking, be sure to press
the service switch to stop the
operation).
Check the refrigerating cycle.
Check the outdoor electrical parts.
Check the indoor electrical parts.
Check to see whether the F-
cable is connected incorrectly
or disconnected
See Out door unit self-diagnosis lamp
lighting mode .
See Troubleshooting when the timer lamp
blinks .
Is approx. DC 33 to 37V being generated? Is the
polarity correct?
Remove the terminal cover and check the voltage
between terminal (C) and terminal (D)
Service switch
P.W.B
Self diagnosis lamps
(LD303, 302, 301)
CN17
IC3
022527
Summary of Contents for RAC-50NH5
Page 32: ... 30 CONSTRUCTION AND DIMENSIONAL DIAGRAM ...
Page 33: ... 31 CONSTRUCTION AND DIMENSIONAL DIAGRAM FOR OUTDOOR MODEL RAC 50NH5 ...
Page 38: ... 39 ...
Page 39: ... 41 ...
Page 40: ... 43 ...
Page 41: ... 44 MODEL RAK 50NH5 RECEIVING P W B MARKING ON P W B COMPONENT SIDE SOLDERING SIDE ...
Page 42: ... 45 MAIN P W B ...
Page 43: ... 47 ...
Page 44: ... 49 ...
Page 46: ... 53 ...
Page 47: ... 55 ...
Page 48: ... 57 ...
Page 49: ... 59 ...
Page 50: ... 61 ...
Page 52: ... 64 N O I T C N U F G N I W S O T U A ...
Page 53: ... 65 RAK 50NH5 ...
Page 56: ... 68 ...
Page 58: ... 70 ...
Page 59: ... 71 ...
Page 60: ... 72 ...
Page 61: ... 73 ...
Page 62: ... 74 ...
Page 63: ... 75 ...
Page 64: ... 76 ...
Page 65: ... 77 ...
Page 66: ... 78 ...
Page 67: ... 79 ...
Page 68: ... 80 ...
Page 70: ... 82 ...
Page 71: ... 83 6 Rotor magnetic pole position detection circuit Ð Ð Ð Ð ...
Page 72: ... 84 7 Drive Circuit ...
Page 73: ... 85 Low speed rotation mode High speed rotation mode ...
Page 74: ... 86 8 HIC and Peripheral Circuits ...
Page 75: ... 87 ...
Page 76: ... 88 1 ...
Page 77: ... 89 2 5 ...
Page 78: ... 90 Ð Ð Ð Ð ...
Page 79: ... 91 9 Temperature Detection Circuit ...
Page 80: ... 92 10 Reset Circuit Ò Ó Ò Ó Ò Ó Ð ...
Page 81: ... 93 Ð 11 Outdoor DC Fan Motor control circuit Ð Ð ...
Page 83: ... 95 12 Power Factor Control Circuit ...
Page 84: ... 96 ...
Page 86: ... 98 OTHERS Q15 A15 Q16 A16 Q17 A17 Q18 A18 Q19 A19 ...
Page 87: ... 99 TROUBLE SHOOTING Model RAK 50NH5 RAC 50NH5 M ...
Page 91: ... 103 SELF DIAGNOSIS LIGHTING MODE ...
Page 97: ... 109 ...
Page 99: ... 111 ...
Page 100: ... 112 ...
Page 109: ... 121 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAK 50NH5 ...
Page 111: ... 123 ...
Page 113: ...RAK 50NH5 RAC 50NH5 HITACHI PM NO 0302E Printed in Malaysia ...