[ Situation ] The compressor will not run (the same state as the thermometer turned off), the product receives remote control
signals normally. The self-diagnosis lamp (LD301) of the outdoor unit blinks once or becomes turned off.
[ Estimated failure locations ]
・
Room temperature thermistor, heat exchanger thermistor
・
Microcomputer peripheral circuit
[ Diagnosis flow ]
Initiating troubleshooting
3. Failure phenomenon: The compressor will not run.
Is the "timer lamp" (orange) of the indoor unit
blinking?
Yes
Yes
Yes
No
No
No
Check for failures according to the self-
diagnosis display.
Did the self-diagnosis lamp (LD301) of the outdoor
unit blink once or become turned off?
Check for failures according to the self-
diagnosis display.
Remove the connector (CN4) of the room
temperature thermistor and heat exchanger
thermistor and measure the thermistor resistance.
Did the reading roughly agree with the resistance
values indicated in the right-hand figure?
Replace the "room temperature and heat
exchanger thermistors".
Thermistor characteristics (resistance)
Ther
mistor resistance
Thermistor temperature
Replace the "indoor electrical unit".
91
Summary of Contents for RAC-25FPA
Page 2: ... DANGER 2 ...
Page 32: ...WIRING DIAGRAM OF THE PRINTED WIRING BOARD Remote controller RAR 5E2 32 ...
Page 33: ...MODEL RAF 25RPA RAC 35RPA 33 ...
Page 34: ...MODEL RAC 25FPA RAC 35FPA 34 ...
Page 39: ...39 ...
Page 41: ...41 ...
Page 44: ...44 ...
Page 59: ...10 10 10 10 R921 R924 R642 R544 R542 R610 R922 DSW1 DSW1 R923 R541 R543 100 59 ...
Page 77: ... 3 3 1 77 ...
Page 82: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25 A RAC 35 A FP FP 82 ...
Page 98: ...98 36 ...
Page 99: ...99 ...
Page 100: ...100 59 ...
Page 101: ...101 ...
Page 113: ...38 39 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAF 25 35RPA 113 ...
Page 114: ...114 HWRAF 50NX2 A14 HBOARD AS ...
Page 117: ...RAF 25RPA RAC 25FPA RAF 35RPA RAC 35FPA HHAW NO 0069E 117 2 ...