1. Failure phenomenon: The power will not become turned on.
>
Situation
@ǂ
Neither initialization, remote control, nor any other step works on the vane position at power-on.
[ Estimated failure
locations ]
·
3.15 A fuse blown out
·
Control power circuit
·
Connector loose, wire break
>
Cautions
@
>
Diagnosis flow
@
Initiating troubleshooting
Replace the 3.15A Fuse of outdoor ele, parts.
Replace the varistor 5 of outdoor ele,parts.
Abnormal
Is the power supply voltage normal?
Normal power supply voltage:230V AC .
Is a voltage of 230V AC applied between the outdoor terminal
tab A-B.
Is a voltage of 32-38V DC applied between the outdoor terminal
tab C-D.
Estimated cause of fuse blowout
·
Abnormally high voltage applied to the power supply
·
Indoor fan motor out of order
·
Power circuit out of order
·
Before work, check the power supply voltage. An abnormal voltage may be being supplied in
some rare occasions due to a defect in the indoor wiring (a wire break in the neutral wire of the
single-phase 3-wire power supply).
·
If the 3.15 A fuse has blown out, eliminate the cause of the fuse blowout. Otherwise, there will occur
another fuse blowout.
·
If the 3.15 A fuse has blown out due to an abnormally high voltage to the power supply, the varistor
(VA001) will deteriorate and become destroyed as well.
·
On a repair service visit due to the failure phenomenon of "The power will not become turned on",
take a "3.15 A fuse" and a "varistor" with you.
Power cord line confirm.
The terminal confirm.
Replace the control P.W.B.
Indoor/Outdoor F-cable’s C-D is correct
connected?
Is the CN3 securely connected?
Replace the terminal.
Get the indoor wiring back to its
normal condition, then conduct
a final check.
F-cable Fix
Check the outdoor
ele. parts.
Yes
No
No
No
No
Yes
Yes
Yes
Normal
87
Summary of Contents for RAC-25FPA
Page 2: ... DANGER 2 ...
Page 32: ...WIRING DIAGRAM OF THE PRINTED WIRING BOARD Remote controller RAR 5E2 32 ...
Page 33: ...MODEL RAF 25RPA RAC 35RPA 33 ...
Page 34: ...MODEL RAC 25FPA RAC 35FPA 34 ...
Page 39: ...39 ...
Page 41: ...41 ...
Page 44: ...44 ...
Page 59: ...10 10 10 10 R921 R924 R642 R544 R542 R610 R922 DSW1 DSW1 R923 R541 R543 100 59 ...
Page 77: ... 3 3 1 77 ...
Page 82: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25 A RAC 35 A FP FP 82 ...
Page 98: ...98 36 ...
Page 99: ...99 ...
Page 100: ...100 59 ...
Page 101: ...101 ...
Page 113: ...38 39 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAF 25 35RPA 113 ...
Page 114: ...114 HWRAF 50NX2 A14 HBOARD AS ...
Page 117: ...RAF 25RPA RAC 25FPA RAF 35RPA RAC 35FPA HHAW NO 0069E 117 2 ...