LD301 blinks 7 times.
Thermistor abnormal.
Is the thermistor connector
disconnected?
*
The problem may be
“forgetting to connect after
servicing”.
Is the continuity of the
thermistor normal?
Connect the thermistor
.
Replace the thermistor
.
Replace parts in the
Ye
s
Y
e
s
Ye
s
No
No
No
control P.W.B.
108