< Troubleshooting by using the self-diagnosis memory function>
・
By using the self-diagnosis memory function, you can check the failure mode (
※
1) occurring in the outdoor electrical
parts on the indoor unit side.
Steps
1. Clear the troubleshooting data.
2. Run the product for several minutes under the conditions where the compressor runs.
3. Redisplay and check the data written in the self-diagnosis memory.
・
The self-diagnosis memory function can also be used to catch sporadic failure phenomena.
Steps
1. Clear the troubleshooting data.
2. Have the user use the product as usual until a failure phenomenon occurs.
(The period depends on the incidence of the phenomenon.)
3. At a later date, redisplay and check the data written in the self-diagnosis memory.
・
For the outdoor self-diagnosis display (OH thermistor heat-up, overload lower limit cut) stemming from the freezing cycle
or operating condition, the time lag is long from operation startup to the emergence of the phenomenon.
Moreover, it is affected by the temperature, sunshine, operating hours, and other factors of the day, so that the
phenomenon may not be able to be identified at the time of a repair service visit. In that case too, use the self-diagnosis
memory function (
※
2).
・
The outdoor self-diagnosis display "overload lower limit cut" and "OH thermistor heat-up" can be identified only when you
are using the self-diagnosis lamp of the outdoor unit and the self-diagnosis memory function of the indoor unit.
Note that this will not be automatically displayed on the indoor unit side.
Initiating troubleshooting
Yes
Perform troubleshooting according to the
self-diagnosis display.
No
No
No
No
※1
※1
※2
Are the "timer lamp" (orange) of the indoor unit
blinking?
The product will begin to run in response to a remote
control setting: "cooling mode, temperature setting 16
℃
"
(summer) or "heating mode, temperature setting 32
℃
"
(winter).
Has the "operation lamp" been turned on?
Yes
Yes
Yes
Check the indoor electrical parts.
Is the compressor running?
Turn off the power and turn on the power and
press the "forcible cooling" switch to operate the
product.
Has the compressor started to run?
Check the freezing cycle.
Check the outdoor electrical parts.
Diagnosis and troubleshooting of indoor electric parts, outdoor electric parts and refrigerating cycle
85
Summary of Contents for RAC-25FPA
Page 2: ... DANGER 2 ...
Page 32: ...WIRING DIAGRAM OF THE PRINTED WIRING BOARD Remote controller RAR 5E2 32 ...
Page 33: ...MODEL RAF 25RPA RAC 35RPA 33 ...
Page 34: ...MODEL RAC 25FPA RAC 35FPA 34 ...
Page 39: ...39 ...
Page 41: ...41 ...
Page 44: ...44 ...
Page 59: ...10 10 10 10 R921 R924 R642 R544 R542 R610 R922 DSW1 DSW1 R923 R541 R543 100 59 ...
Page 77: ... 3 3 1 77 ...
Page 82: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25 A RAC 35 A FP FP 82 ...
Page 98: ...98 36 ...
Page 99: ...99 ...
Page 100: ...100 59 ...
Page 101: ...101 ...
Page 113: ...38 39 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAF 25 35RPA 113 ...
Page 114: ...114 HWRAF 50NX2 A14 HBOARD AS ...
Page 117: ...RAF 25RPA RAC 25FPA RAF 35RPA RAC 35FPA HHAW NO 0069E 117 2 ...