– 33 –
5. Initial Setting Circuit (IC401)
•
When power is supplied, the microcomputer reads the data in IC401 or IC402 (E
2
PROM) and sets
the preheating activation value and the rating and maximum speed of the compressor, etc. to their
initial values.
•
Data of self-diagnosis mode is stored in IC401 or IC402; data will not be erased even when power is
turned off.
6. Power Supply
First, 35V power which operates the indoor unit is generated by the power source section of the outdoor unit and
supplied to the indoor unit through the C and D lines of the connecting cable.
Second, use the DC/DC converter and the 35 V power supply from the outdoor unit to generate 12 V control
power, which drives the stepping motor during the operation.
In addition, use the regulator IC 121 to generate 5 V power required for driving the micro computer and controlling
fan motor.
If the terminal block was overheated due to a connecting cable improper connection, the thermal fuse built in the
terminal block will burnt to shut off the 12 V line and stop the operation of the indoor unit. Then, the outdoor unit
cannot be communicated with the indoor unit and a communication error occurs (the outdoor LD301 will blink 9
times), stop all operations.
Fig. 6-1
Fig. 5-1
Microcomputer
External ROM
SCL
SDA
0V
0V
0V
5V
5V
5V
C401
IC401 or IC402 (E
2
PROM)
R404
R403
27
26
1
2
3
4
8
7
6
5
}
Summary of Contents for RAC-14EH2
Page 22: ...RAS 14EH2 CIRCUIT DIAGRAM 20 07K394_RAS 14EH2_020 021_A2_E 2007 10 31 17 19 20 ...
Page 25: ... 23 button 25 26 26 27 28 26 RAS 14EH2 07K394_RAS 14EH2_023_A3_E 2007 10 31 16 45 23 ...
Page 92: ... 90 07K394_RAS 14EH2_083 092_E 2007 11 12 09 12 90 ...
Page 94: ... 92 07K394_RAS 14EH2_083 092_E 2007 11 12 09 12 92 ...
Page 95: ...HITACHI AW NO 0029E RAS 14EH2 RAC 14EH2 07K394_RAS 14EH2_000cover_E 2007 10 31 17 14 3 ...