![Hitachi P-N23NA2 Installation And Operation Manual Download Page 41](http://html.mh-extra.com/html/hitachi/p-n23na2/p-n23na2_installation-and-operation-manual_139473041.webp)
4 REFRIGERANT PIPING
4.1 PIPING CONNECTION
4.1.1
Piping Position
(mm)
84
90
76
95
160
157
140
ø30
(Liquid pipe)
(Gas pipe)
(Gas pipe)
(Liquid pipe)
(mm)
84
90
76
95
160
157
140
ø30
Gas pipe connection
Liquid pipe connection
(Gas pipe)
(Liquid pipe)
4.1.2
Size of piping connection
Piping size
mm (in)
Liquid piping
Gas piping
RCI-(1.0-2.0)
Ø 6.35 (1/4)
Ø 12.70 (1/2)
RCI-(2.5-6.0)
Ø 9.52 (3/8)
Ø 15.88 (5/8)
Thickness of Copper Pipes
Ø (in)
Ø (mm)
Thickness (mm)
1/4
6.35
0.80
3/8
9.53
0.80
1/2
12.70
0.80
5/8
15.88
1.00
Flare Pipe Dimensions
Ø (in)
Ø (mm)
A +0/-0.4
(mm)
1/4
6.35
9.1
3/8
9.52
13.2
1/2
12.70
16.6
5/8
15.88
19.7
Flare Nut Dimensions
Nominal
diameter (in)
Nominal
diameter
(mm)
B (mm)
1/4
6.35
17
3/8
9.53
22
1/2
12.70
26
5/8
15.88
29
5 DRAIN PIPING
5.1 GENERAL INFORMATION
I
NCORRECT
CORRECT
Incorrect: Upward Slope
Incorrect: Rising Part
Common drain piping (Min.VP30)
Vinyl chloride pipe (VP25)
Min. 100mm
(higher as possible)
Drain piping of unit side
(Down slope from rising part)
This drain piping shall
be separating from
others pipes
1/25 to 1/100
Down-Slope
REFRIGERANT PIPING
PMML0547 rev.0 - 11/2020
7
EN
Summary of Contents for P-N23NA2
Page 2: ......
Page 50: ......
Page 66: ......
Page 82: ......
Page 98: ......
Page 114: ......
Page 130: ......
Page 146: ......
Page 162: ......
Page 178: ......
Page 194: ......
Page 210: ......
Page 226: ......
Page 242: ......
Page 258: ......
Page 274: ......
Page 290: ......
Page 306: ......
Page 322: ......
Page 338: ......
Page 339: ......