14
5.5.1 Driving with the standard panel
RUN/STOP/RESET key on the standard operation panel is effective regardless of the setting of the driving order method(A002).
Thus, the following
operation method (1) to (3) is possible without an option if it is an initial value.
(1)Method to perform driving in RUN/STOP/RESET key and perform frequency setting in Multispeed select
This is the operation method using Run command is given by "RUN/STOP/RESET key"
& Frequency setting is given by Fixed value such as 20/40/60Hz, Accel&Decel time is
10 seconds. If you don't need to change parameters such as Accel&Decel time, the
optional Operator is not required.) To use the set Freq. setting, use the Multi-speed
default frequency setting (1=60Hz),(2=40Hz),(3=20Hz).
■
Setup
Function Name
Code
Data
Note
Input [3] function
C003
02(CF1)
Default
Input [4] function
C004
03(CF2)
The initial value of Acceleration/ Deceleration time is 10sec.
Please change the following parameters as needed.
Function Name
Code
Setting Range
Note
Acceleration time
F002
0.00 to 3600sec.
Default
:
10 sec.
Deceleration time
F003
0.00 to 3600sec.
Default
:
10 sec.
※
One of the following is required when changing parameters on NE-S1 series inverters.
①
Dedicated operator (NES1-OP)
②
Digital operator
③
5-line LCD operator
④
Modbus
⑤
PC programming tool (ProDriveNext)
(2) Method to perform driving in RUN/STOP/RESET key and perform frequency setting in speed potentiometer
This is the operation method using Run command is given by "RUN/STOP/RESET key" & Frequency setting is given by analog input such as
O-L voltage, Accel&Decel time is 10 seconds. If you don't need to change parameter such as Accel&Decel time, the optional Operator is not required.)
Below diagram is to set the external Freq. setting connecting H-O-L volume to supply O-L voltage.
■
Setup
Function Name
Code
Data
Note
Frequency source
A001
01(Control circuit terminals)
Default
The initial value of Acceleration/ Deceleration time is 10sec.
Please change the following parameters as needed.
Function Name
Code
Setting Range
Note
Acceleration time
F002
0.00 to 3600 sec.
default
:
10 sec.
Deceleration time
F003
0.00 to 3600 sec.
default
:
10 sec.
※
One of the following is required when changing default parameters on NE-S1 series
inverters.
②
Dedicated operator (NES1-OP)
②
Digital operator
③
5-line LCD operator
④
Modbus
⑤
PC programming tool (ProDriveNext)
(3) Method to perform driving in FW/RV teraminal and perform frequency setting in volume resistor
This is the operation method using Run command is given by intelligent input terminal such as FW(RV) function & Frequency setting is given by
analog input such as O-L voltage. If you don't need to change such as Accel&Decel time, optional Operator is not required.) Below diagram is to set
the external Freq. setting connecting H-O-L volume to supply O-L voltage.
■
Setup
Function Name
Code
Data
Note
Frequency source
A001
01(Control circuit terminals)
Default
Run command source
A002
01(Control circuit terminals)
Default
Input [1] function
C001
00(FW)
Default
Input [2] function
C002
01(RV)
The initial value of Acceleration/ Deceleration time is 10sec.
Please change the following parameters as needed.
Function Name
Code
Setting Range
Note
Acceleration time
F002
0.00 to 3600 sec.
Default
:
10 sec.
Deceleration time
F003
0.00 to 3600 sec.
Default
:
10 sec.
※
One of the following is required when changing default parameters on NE-S1 series
inverters.
①
Dedicated operator (NES1-OP)
②
Digital operator
③
5-line LCD operator
④
Modbus
⑤
PC programming tool (ProDriveNext)
■
Example of use(default)
Intelligent input
terminal [3]
Intelligent input
terminal [4]
60Hz order
OFF
ON
40Hz order
ON
OFF
20Hz order
ON
ON
■
Control circuit terminals wiring
P24
PLC
L
3
CF1
CF2
4
…
Note)
The above is a method to perform analog
input(O/OI) by voltage input.
It is necessary for
SW6 on the board to be set for voltage
input(default).
→
P9
■
Control circuit terminals wiring
P24
PLC
L
1
2
L
O/OI
H
FW
RV
Frequency setting
resistor
P24
PLC
L
O/OI
H
Frequency setting
resistor
Note)
The above is a method to perform analog
input(O/OI) by voltage input.
It is necessary for
SW6 on the board to be set for voltage
input(default).
→
P9
■
Control circuit terminals wiring