5.4 Names and functions of components 

 
Standard panel 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Name 

Description 

POWER LED 

- Turns on (red) during inverter is powered up 

Run command LED 

- Turns on (green) during inverter operation. (This turns ON either Run command is given, or the inverter is giving 

out power. Therefore it keeps turning on during 0 Hz driving, or keeps turning on during deceleration period even 

after the run command is OFF. 

ALARM LED 

- Turns on (red) when the inverter is in trip status. 

- Refer to section 6.8 of QRG how to reset the trip status. 

Key valid lamp 

-  Turns  on  (green)  when  the  RUN/STOP/RESET  is  ready.  It  turns  off  when  there  is  a  RUN  command.  If  the  run 

command is being given from the RUN/STOP/RESET key, the lamp is being on during deceleration period even 

after the run command is OFF. While Run command is given such as FW(RV) terminal,if "RUN/STOP/RESET key" 

was pressed, even Run command is OFF, the "Key valid lamp" is OFF until inverter is Stopped.

 

RUN/STOP/RESET key 

-

 Makes inverter run, stop and reset. RUN/STOP/RESET key is set default and it can be made invalid by the key 

sensitivity selection (C151) to “no”. 

- It restores from the trip state if the inverter is in trip state. 

- If the ModBus communication is selected, it can be temporary changed to an external operator mode if the inverter 

is  powered  up  with  pressing  the RUN/STOP/RESET key

 

and  keep  it  pressing  5seconds,and  take off from  the 

key.. Changeover switch must be changed later on.    Note 1)

 

RS422/RS485 port (RJ45) 

-  This  is  a  port  for  external  operator,  Modbus  connection,  or  ProDrioveNext  (RS485/operator  changeover  switch 

must be operated) before Power ON. In case of Modbus communication, it is necessary to set the changeover 

switch and parameter (C070). Display of NES1-OP will be according to the parameter set of b150 continuously, if 

the external operator is connected while the dedicated operator (NES1-OP) is integrated.    Note2) 

Note 1) It is necessary to set changeover switch and the parameter C070 for releasing the Modbus communication. If the parameter C070 is 

set to ModBus, external operator via the RS45 jack cannot be used. 

Note 2) Connecting to the RJ45 jack must be done during the inverter power off. 

 

5.5 Motor operation 

 

Both “Run command” and “frequency command” is necessary to run the motor. Motor does not run if one of each is missing. For example, motor will 

not run when a run command is given, but a frequency command is 0Hz. Additionally, the motor will not run if a FRS (free run stop) signal (and the like) 

is being given. 

NE-S1  series  inverter  has  following  way  to  set  the  run  command  and  frequency  command.  (This  is  an  example  of  sink  logic  and  uses  internal 

control power supply.) 

 

Driving method in the default

5.5.1

 

POWER LED 

ALARM LED 

Run command LED 

RS422/RS485 port (RJ45) 

Key valid lamp 

RUN/STOP/RESET key 

Summary of Contents for NE-S1 series

Page 1: ...nd QRG Quick Reference Guide and understand perfectly how to handle properly and the safety cautions of the product before operation for safety and proper usage Note that this Manual is intended for each product and should be delivered to the end user of the inverter NT341BX Many of the drawings in the Instruction Manual show the inverter with covers and or parts blocking your view being removed D...

Page 2: ...cility can be operated Otherwise you run the risk of injury or damage to the machine controlled by the inverter Do not touch the heat sink which heats up during the inverter operation Otherwise you run the risk of burn injury The inverter allows you to easily control the speed of motor or machine operations Before operating the inverter confirm the capacity and ratings of the motor or machine cont...

Page 3: ...tection required at end application h Use 60 75ºC CU wire only i Tightening torque and wire range as shown in the table below Model No Required Torque N m Wire Range AWG NES1 002S 0 8 1 0 16 14 NES1 004S 0 8 1 0 16 14 NES1 007S 1 8 14 12 NES1 015S 1 8 12 10 NES1 022S 1 8 10 NES1 002L 0 8 1 0 16 14 NES1 004L 0 8 1 0 16 14 NES1 007L 0 8 1 0 16 14 NES1 015L 1 8 14 NES1 022L 1 8 12 j Distribution fuse...

Page 4: ... name of the inverter 2 Manufacturing number 3 When you bought the product 4 Contents of your inquiry Damaged portion and condition and else 1 4 Warranty Terms The warranty period under normal installation and handling conditions shall be two 2 years from the date of manufacture or one 1 year from the date of installation whichever occurs first The warranty shall cover the repair or replacement at...

Page 5: ...lease be sure to check that this lamp is turned OFF after waiting 10 minutes of power OFF Note1 Refer to page 13 for the description of the display and key operation Note 2 Position of charge lamp depends on the model Refer to page 11 for the details Note 3 Pay attention when operating by PC via RS422 RS485 port as the operation can also be done from the panel of the inverter Note 4 Be sure to tur...

Page 6: ...g is generated inside the inverter electronic parts are short circuited each other to cause a failure Also please avoid installing it in direct sunlight Caution for installation environment Please avoid installing the inverter in such places where dust corrosive gas explosive gas flammable gas mist of grinding fluid or salt pollution etc exists Invasion of dust dirt etc into the inverter may cause...

Page 7: ...C software ProDriveNext See above for the position of the window Be sure to make window after removing the front cover There are cutouts at the window so it can be removed easily by pressing up side and bottom side of the window alternatively The window cannot be restored if it is once opened Please use commercially supplied RJ45 connector cap or the like if necessary 3 How to attach Press the fro...

Page 8: ... G Earth terminal To make grounding Be sure to make this grounding to avoid electric shock and for improving the EMC performance The terminal is located on the heatsink Intelligent inputs 7 terminals 0 10VDC 10bit PLC P24 DC24V L P H O OI Category D grounding 200V class DC10V 5 2 1 3 4 Intelligent input terminal 11 CM2 Relay contacts AL0 AL1 AL2 L DC10V 10mA Max 4 7kΩ 4 7kΩ L FM L Pulse train outp...

Page 9: ...gent output terminals One function from 28 available functions can be assigned Refer to section 7 3 of QRG for the details Open collector output Between 11 and CM2 Voltage drop during ON 4V or less Max allowable voltage 27V Max allowable current 50mA CM2 Commonfor intelligent output terminals Common for the terminal 11 Max allowable current 100mA Relay AL0 AL1 AL2 Intelligent relay outputs One fun...

Page 10: ... An inverter run by a private power generator may overheat the generator or suffer from a deformed output voltage waveform of the generator Generally the generator capacity should be five times that of the inverter kVA in a PWM control system or six times greater in a PAM control system In the case of important equipment to shorten the non operational time of inverter failure please provide a back...

Page 11: ...AWG14 2 0 M3 5 7 6 1 0 EX30 10A H10C 10A 0 75 007SB AWG14 2 0 M4 10 1 4 EX30 15A H10C 15A 1 5 015SB AWG10 5 5 M4 10 1 4 EX30 20A H20 20A 2 2 022SB AWG10 5 5 M4 10 1 4 EX30 20A H20 30A 3 phase 200V 0 2 002LB AWG16 1 25 M3 5 7 6 1 0 EX30 5A H10C 10A 0 4 004LB AWG16 1 25 M3 5 7 6 1 0 EX30 10A H10C 10A 0 75 007LB AWG16 1 25 M3 5 7 6 1 0 EX30 10A H10C 15A 1 5 015LB AWG14 2 0 M4 10 1 4 EX30 15A H10C 15A...

Page 12: ...for each operator for the detailed information 3 5 line LCD operator WOP WOP having serial number of 16918938000081 or later 2011 07 production is applied to NE S1 series inverter English only WOP can be used with connector cable ICS 1 3 and connected to the RS422 RS485 port RJ45 in the inverter Turn the changeover switch to the operator side OFF side in that case See page 9 Refer to the manual fo...

Page 13: ...red up with pressing the RUN STOP RESET key and keep it pressing 5seconds and take off from the key Changeover switch must be changed later on Note 1 RS422 RS485 port RJ45 This is a port for external operator Modbus connection or ProDrioveNext RS485 operator changeover switch must be operated before Power ON In case of Modbus communication it is necessary to set the changeover switch and parameter...

Page 14: ...meters as needed Function Name Code Setting Range Note Acceleration time F002 0 00 to 3600 sec default 10 sec Deceleration time F003 0 00 to 3600 sec default 10 sec One of the following is required when changing default parameters on NE S1 series inverters Dedicated operator NES1 OP Digital operator 5 line LCD operator Modbus PC programming tool ProDriveNext 3 Method to perform driving in FW RV te...

Page 15: ...gital input signal 3 wire input possible Modbus Option Operator Dedicated Operator Intelligent input terminal 5terminals Analog input 1terminal O OI terminal Voltage input10bit 0 to 10V Current input 10bit 0 to 20mA selected with a selection switch Output signal Intelligent output terminal 5 open collector output terminals 1 relay 1 from c contact output terminal Pulse Output 1terminal connection ...

Page 16: ...use applicable to the products NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS AND THAT THE HITACHI INDUSTRIAL EQUIPMENT SYSTEMS PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM See also product catalogs Model W mm H mm D mm D1...

Reviews: