CAPACITIES AND SELECTION DATA
3-30
3.3. CORRECTION FACTORS ACCORDING TO PIPING LENGTH
Correction Factor for
Cooling Capacity
according to
Piping Length
The cooling capacity should be corrected according to the
following formula:
CCA = CC x F
CCA: Actual Corrected Cooling Capacity
(kcal/h)
CC: Cooling Capacity in the Performance
Table (kcal/h)
F:
Correction Factor Based on the
Equivalent Piping Length
Correction Factor for
Heating Capacity
according to
Piping Length
The heating capacity should be corrected according to the
following formula:
HCA= HC x F
HCA: Actual Corrected Heating Capacity
(kcal/h)
HC: Heating Capacity in the Performance
Table (kcal/h)
F:
Correction Factor Based on the
Equivalent Piping Length
The correction factors are shown in the following figure.
Equivalent Piping Length for:
– One 90º Elbow is 0.5m.
– One 180º Curve is 1.5m.
H:
Vertical Distance Between Indoor Unit and Outdoor
Units in Meters
L:
Actual One-Way Piping Length Between Indoor Unit
and Outdoor Unit in Meters
EL:
Equivalent Total Distance Between Indoor Unit and
Outdoor Unit in Meters
(Equivalent One-Way Piping Length)
H
L
Summary of Contents for MULTIZONE RAM-40NE2F
Page 11: ...DIMENSIONAL DATA 2 3 2 2 MULTIZONE OUTDOOR UNITS 2 2 1 2 ROOMS MULTIZONE RAM 40NE2F ...
Page 12: ...DIMENSIONAL DATA 2 4 2 2 2 2 ROOMS MULTIZONE RAM 53NE2F Unit mm ...
Page 13: ...DIMENSIONAL DATA 2 5 2 2 3 3 ROOMS MULTIZONE RAM 53NE3F Unit mm ...
Page 63: ...WIRING DIAGRAM 7 2 7 1 MULTIZONE 7 1 1 RAK 15QEF RAK 18REF RAK 25REF RAK 35REF RAK 50REF ...
Page 64: ...WIRING DIAGRAM 7 3 7 1 2 RAM 40NE2F RAM 53NE2F ...
Page 65: ...WIRING DIAGRAM 7 4 7 1 3 RAM 53NE3F ...
Page 68: ...REFRIGERANT CYCLE CYC8 3L 8 1 2 WALL TYPE RAK 50REF ...
Page 69: ...REFRIGERANT CYCLE 8 4 8 2 MULTIZONE OUTDOOR UNITS 8 2 1 2 ROOMS MULTIZONE RAM 40NE2F ...
Page 70: ...REFRIGERANT CYCLE CYC8 5L 8 2 3 2 ROOMS MULTIZONE RAM 53NE2F φ12 7 ...
Page 71: ...REFRIGERANT CYCLE 8 6 8 2 4 3 ROOMS MULTIZONE RAM 53NE3F ...
Page 74: ...CONTROL AND FUNCTION 9 3 9 2 SHIFT VALUE ...
Page 75: ...9 4 CONTROL AND FUNCTION 9 3 DISPLAY OPERATION MODE SETTING ...
Page 76: ...CONTROL AND FUNCTION 9 5 9 4 HOW TO CHANGE THE INTERMITTENT FAN CONTROL SETTING ...
Page 77: ...9 6 CONTROL AND FUNCTION 9 5 HOW TO CHANGE THE FAN SPEED IN COOLING MODE DURING THERMO OFF ...
Page 78: ...CONTROL AND FUNCTION 9 7 9 6 SETTING THE PREVENTION OF MUTUAL INTERFERENCE ...