9-8
CONTROL AND FUNCTION
9.7
ERROR CODE INFORMATION
9.7.1
HOW TO DISPLAY ERROR CODE
1. Set the remote to “OFF”.
2. Press
(MODE) button on the remote control to set it to
mode.
3. Press
(TEMPERATURE) button of the remote control and set the room temperature on the remote control to 32
℃
.
4. Hold down press
(TEMPERATURE) button for about 2 seconds, then press the
(ON/OFF) button.
5. Transmission sign lights up with beep from indoor unit simultaneously and the error code will be displayed.
6. Use the wind speed button to set the fan speed according to the required fault information (See the table below
TIMER LAMP BLINKING
LED301 BLINKING
CODE
MEANING
IN
D
O
O
R
-
-
000
00
Normal
1 time
001
00
Refrigerant cycle fault
2 times
-
-
Outdoor unit is under forced operation
3 times
9 times
003
00
Communication error between indoor and outdoor
units
9 times
-
009
00
Indoor thermistor
10 times
-
010
00
Abnormal rotating numbers
12 times
9 times
012
00
Communication error between indoor and
outdoor units
13 times
-
013
00
EEPROM data reading error
18 times
-
018
00
Cleaning defective
O
U
T
D
O
O
R
4 times
2 times
002
01
Peak current cut
4 times
3 times
003
01
Compressor abnormal low speed rotation
4 times
4 times
004
01
Compressor switching failure
4 times
5 times
005
01
Overload lower limit cut
4 times
6 times
006
01
OH thermistor temperature rise
4 times
7 times
007
01
Abnormal outdoor thermistor
4 times
9 times
009
01
Communication error
Summary of Contents for MULTIZONE RAM-40NE2F
Page 11: ...DIMENSIONAL DATA 2 3 2 2 MULTIZONE OUTDOOR UNITS 2 2 1 2 ROOMS MULTIZONE RAM 40NE2F ...
Page 12: ...DIMENSIONAL DATA 2 4 2 2 2 2 ROOMS MULTIZONE RAM 53NE2F Unit mm ...
Page 13: ...DIMENSIONAL DATA 2 5 2 2 3 3 ROOMS MULTIZONE RAM 53NE3F Unit mm ...
Page 63: ...WIRING DIAGRAM 7 2 7 1 MULTIZONE 7 1 1 RAK 15QEF RAK 18REF RAK 25REF RAK 35REF RAK 50REF ...
Page 64: ...WIRING DIAGRAM 7 3 7 1 2 RAM 40NE2F RAM 53NE2F ...
Page 65: ...WIRING DIAGRAM 7 4 7 1 3 RAM 53NE3F ...
Page 68: ...REFRIGERANT CYCLE CYC8 3L 8 1 2 WALL TYPE RAK 50REF ...
Page 69: ...REFRIGERANT CYCLE 8 4 8 2 MULTIZONE OUTDOOR UNITS 8 2 1 2 ROOMS MULTIZONE RAM 40NE2F ...
Page 70: ...REFRIGERANT CYCLE CYC8 5L 8 2 3 2 ROOMS MULTIZONE RAM 53NE2F φ12 7 ...
Page 71: ...REFRIGERANT CYCLE 8 6 8 2 4 3 ROOMS MULTIZONE RAM 53NE3F ...
Page 74: ...CONTROL AND FUNCTION 9 3 9 2 SHIFT VALUE ...
Page 75: ...9 4 CONTROL AND FUNCTION 9 3 DISPLAY OPERATION MODE SETTING ...
Page 76: ...CONTROL AND FUNCTION 9 5 9 4 HOW TO CHANGE THE INTERMITTENT FAN CONTROL SETTING ...
Page 77: ...9 6 CONTROL AND FUNCTION 9 5 HOW TO CHANGE THE FAN SPEED IN COOLING MODE DURING THERMO OFF ...
Page 78: ...CONTROL AND FUNCTION 9 7 9 6 SETTING THE PREVENTION OF MUTUAL INTERFERENCE ...