5.3 Cable
Specifications
The transmission cables, power cables, and grounding cables should satisfy the following:
Item Specifications
Remarks
Transmission cable
Characteristic
impedance
100
Ω
Wire size
0.5 mm
2
Maximum conductor
resistance
34.0
Ω
/km 20
℃
Withstanding voltage
1000 VAC/1 minute
Minimum insulation
resistance
2500 M
Ω・
km 20
℃
Static capacity
50 pF/m
1 kHz
Recommended cable
type
KPEV-SB 2P 0.5 mm
2
Made by Hitachi
Cable, Ltd.
Power supply cable
Wire type
Shielded twisted-pair cable or
3-core twisted cable
Wire size
2 mm
2
or more
Depending upon loads
and cable lengths
Grounding cable
Wire size
2 mm
2
or more
Use the solderless terminals to connect cables.
<Solderless terminals>
(Unit: mm)
Eyelet type
7 or less
7 or less
Example: R1.25-3
Example: 1.25-YS3A
U-shaped
6
Solderless terminal
Heat-shrinking tube
Cable
Shield cable
<Connecting cable wires to Solderless terminals>